Loading...
HomeMy Public PortalAbout111-2015 - Metro - American Environmental Corp.- Phase 1 Remediation - Part 6L/ DIVISION 11 EQUIPMENT SECTION 11330 REMEDIATION SYSTEM EQUIPMENT PART 1 GENERAL 1.1 DESIGN AND PERFORMANCE REQUIREMENTS The Contractor shall provide equipment, appurtenances, labor, and other materials to design, assemble, and deliver one completely operational remediation system ready to be erected and connected with six (6) dual -phase remediation wells installed as per Section 02521. The equipment is to be housed in an enclosure consistent with Section 13120. Equipment required in this specification will be used to implement high -vacuum dual -phase extraction (HVDPE) remediation technology in the five (5) HVDPE recovery wells as specified in the approved Remediation Work Plan (RWP) and may be implemented in one (1) additional optional well. The principal elements of the equipment shall be selected and specified by the Contractor consistent with these requirements and the requirements listed in the approved RWP. Specific performance criteria that must be achieved by the Contractor's remediation system equipment include the following: 1. The remediation system equipment shall be of sufficient capacity to safely and continuously draw a minimum of 3.1 gallons of liquid from each HVDPE recovery well, for an aggregate minimum capacity of 19 gallons per minute (gpm). 2. Treat a minimum of 19 gpm of petroleum contaminated influent water to safely and continuously achieve non -detectable concentrations as measured using SW-846 Method 8260E or 8260C operating at a 5 ug/I reporting limit. 3. The remediation system equipment shall be of sufficient capacity to safely and continuously draw a minimum of 25 actual cubic feet per minute (ACFM) of air from each HVDPE recovery well for an aggregate minimum capacity of 150 ACFM. 4. The remediation equipment shall be of sufficient capacity to safely and continuously draw air at a vacuum of 25 inches of mercury (2V HgV). 5. Treat a minimum of 150 ACFM of air to safely and continuously achieve petroleum volatile organic compound emissions of less than 3 pounds per hour and 15 pounds per day; and to prevent the occurrence of discernable or nuisance malodorous conditions that might result from the operation of the remediation system equipment at any location. 6. The remediation system equipment shall be of sufficient design, assembly, and construction to safely and continuously operate for a period of at least three (3) years with an operational "up time of at least 95 percent of each calendar month during its operational period. 7. The remediation system equipment will be operable without being unduly noisy when judged by the Owner or Engineer standing in any direction approximately 50 feet from the equipment. K:lwse�►ncuovrrwo nonvsoo- r sitosoow�r cocsti:aio eowv ooc Weaver Consukants Group, LLC 11300 -Page 1 of 3 8. The remedlation system equipment will include continuous electronic monitoring sensors and a device programmed by the Contractor to immediately alert the Contractor and the Engineer in the event of any malfunction. 1.2 SUBMITTALS Prior to procuring or delivering the remediation system equipment, the Contractor will submit detailed plans and specifications for review by the Engineer. All principal equipment to be included in the system will be documented using manufacturer's catalog cuts or other literature specifying all relevant capacities at a minimum. Schematic drawings will be included for general layout of the equipment, electrical controls; and piping, and instrumentation. PART 2 PRODUCTS This part specifies significant equipment and selected appurtenant components needed to assemble the remediation system. It is incumbent upon the Contractor to identify principal and appurtenant equipment; procure, and incorporate into the Work any and all elements required by the Contractor's design, whether specified herein or not. Products related to the system enclosure, such as heater, exhaust fan, lighting, and fire suppression system, are specified in Division 13, Section 13120. PART 3 EXECUTION 3.1 MOUNTING The Contractor shall securely mount the indicated equipment within the above ground system enclosure using means to assure firm attachment during over -the -road transportation, loading, and unloading. This is expected to Include welded or through -bolted mountings sufficient to withstand the anticipated stresses. 3.2 PHYSICAL ARRANGEMENT The Contractor shall physically arrange the equipment within the enclosure as shown in the Contractor's submittal(s). Alternative arrangements will be approved if proposed by the Contractor and found superior by the Engineer. 3.3 FUNCTIONAL INTERCONNECTION The Contractor shall Interconnect the equipment as shown in the Contractor's plans. Details as to interconnections shall be worked out by the Contractor to assure functionality as generally described under the requirements of 1.1 DESIGN AND PERFORMANCE REQUIREMENTS. Interconnection and functionality shall meet the following general criteria: • The remediation equipment control system will immediately shut down the operation in the event of any significant fault or malfunction. wea.+uxrr.o�w.Ra�a,nu�oo�u�3�o.. Weaver Consu#tants Group, iLLC 11300 -Page 2 of 3 • Discharge of the automatic fire suppression system (refer to Section 13120) shall signal the electronic monitor, which shall then immediately alert the Contractor and the Engineer. • The electronic monitor shall immediately alert the Contractor and the Engineer in the event of main power failure. • On loss of main electrical power or malfunction shutdown, the remediation system shall require manual re -setting and re -starting. 3.4 OPERATIONAL TESTING The Contractor shall test the completed system to assure proper and complete operation prior to delivery to the Owner's facility. Testing will include energizing the completed system at its off -site location of assembly. Specific tests shall include the following: • Energized operation • Testing of all fault conditions and shutdown • The fire suppression system discharge indicator shall be verified by manipulating its actuator. • Main power shall be de -energized to the system and operation of the remote electronic monitoring device shall be verified. The Contractor shall verify the results of each test in writing, and supply a written test report with the completed system. END OF SECTION weans rarraa�aa►ar�ar oo, n w.-0o�►cvM,u►u�rnocsu� a Fcurcoc Weaver Consultants Group, LLC 11300 - Page 3 of 3 DIVISION 13 SPECIAL CONSTRUCTION SECTION 13120 ABOVE GROUND SYSTEM ENCLOSURE PART i GENERAL 1.1 REFERENCES The publications listed below form part of this specification to the extent referenced. The publications are referred to within text by basic designation only. #53 Graded Material (2006) Indiana Department of Transportation Standard Specifications, 904.03 Coarse Aggregates 1.2 DESIGN AND PERFORMANCE REQUIREMENTS The Contractor shall provide one above -ground system enclosure for the control elements of the remediation system. An International Standards Organization (ISO) intermodal transportation container, modified as specified herein, will serve as an acceptable enclosure. Other types may be proposed for the Owner's consideration such as a towable trailer or prefabricated mobile building. 1.3 SUBMITTALS Contractor shall provide drawings or photographs of the proposed enclosure and other information sufficient to describe its dimensions, capacities, appearance, and other characteristics to the engineer for approval prior to procurement or proposed delivery. The Owner or Engineer may approve or require that the Contractor provide and alternate proposed enclosure if the Contractor's initial proposal, in the opinion of the Owner or Engineer, is unacceptable in appearance or expected performance. PART 2 PRODUCTS 2.1 MATERIALS One dry freight 20 ft x g"6" ISO intermodal transportation container, front loading, completely enclosed, and weather tight. The basic unit may be new or used; if a used container is provided, it shall be subject to the Owner's inspection and acceptance. A "high -cube" unit is also acceptable. Other types of enclosures may be proposed for consideration by the Owner. 2.2 PAINT COATINGS The enclosure shall be coated with paint of a type and color acceptable to the Owner and Engineer. 2.3 INSULATION The enclosure will be insulated on all exterior walls, ceiling, roof, and floor with insulating material rated a minimum of R-4. ctws�wna ar �nwso�wia�wunru.coc�isam�sv am svi RJMMX Weaver Consuhants Group, LLC 13120 -Page 1 of 3 2.4 ELECTRICAL The enclosure will include a 200-amp electrical service panel (or larger, if required by the proposed equipment) and exterior disconnect ready for connection to underground or overhead electrical service to be provided by the Contractor. 2.5 VENTILATION The enclosure will include an electrically -powered exhaust fan of appropriate capacity for the proposed equipment. McMaster -Carr 192SK2 or approved equal, may be acceptable. Makeup air is to be provided by louvered vents appropriately positioned for ventilation and cooling. McMaster -Carr 2001SK62 or approved equal. To include wiring and switchgear. 2.6 HEATING The basic container unit will be modified to include a wall -mounted forced air heater, 2,000 watts at 240V AC, single phase, approximately 7,000 btu/hr. McMaster -Carr 1726K26 or approved equal, may be acceptable. To include wiring and switchgear. 2.7 LIGHTING The basic container unit will be modified with interior electrical lighting, to include three 484nch fluorescent fixtures, ceiling mounted along center line and evenly spaced end to end. To include wiring and switchgear. McMaster -Carr 1683K14 or approved equal, may be acceptable. To include wiring and switchgear. 2.8 FIRE PROTECTION The Contractor shall equip the enclosure with an automatic fire suppression system, to be located and mounted to the interior of the container unit consistent with manufacturer's instructions. Rreboy- Xintex MA2-1300-FE241 or approved equal of appropriate size for the volumetric capacity of the enclosure. 2.9 FOUNDATION The Contractor shall provide an aggregate pad to support the enclosure. The aggregate pad will be constructed of Indiana Department of Transportation #53-graded material. The material may be natural limestone, dolomite, or select iron -making slag. Approximately 10 cubic yards of material are anticipated to be needed to construct as shown on the Plans. 2.10 TIE -DOWNS Auger or direct -drive tie -down anchors shall be provided for each corner of the enclosure, together with hooks, cables, or straps as needed for enclosure to ground connections. Each anchor and attachment shall be able to withstand 1,500 pounds of pullout stress. K:iWMAaMrMCMUnanOoo- W"MP o,AKW"DOMI9120ASV QM SK&V=X Weaver Consultants Group, LLC 13120 -Page 2 of 3 PART 3 EXECUTION 3.1 ENCLOSURE CONSTRUCTION/PREPARATION The Contractor shall construction/preparation the enclosure as indicated herein prior to delivering it to the Owner's site. In addition to the modifications identified herein, all system components shall also be installed and will be ready to operate upon delivery as further described in Division 11, Section 11300. 3.2 FOUNDATION The Contractor shall prepare the foundation subgrade by blading and vibratory compaction as needed to achieve 95 percent of standard Proctor density to a depth of 12 inches below surface grade. The aggregate pad shall be placed, bladed, and rolled to achieve a 124nch thickness, tapered over a 6-foot distance from the end doors to facilitate access. The aggregate pad will be level and smooth along its upper surface. 3.3 ERECTION The enclosure shall be erected using either a crane to lift it into place, or by using a slide -off delivery trailer, or towed into place if a mobile trailer is used. Regardless of the method, the enclosure shall be erected plumb and level, and will be fully supported along its base. 3.4 TIE DOWNS Direct -drive or auger tie down anchors shall be placed at each comer of the enclosure and affixed to the enclosure using hooks or other appurtenances of sufficient strength to hold the enclosure in place during wind gusts of up to 100 miles per hour. 3.5 ELECTRICAL CONNECTION Connection of the exterior electrical disconnect with utility -provided electrical power to be arranged and installed by the Contractor. 3.6 TESTING AND INSPECTIONS Owner/Engineer shall test and inspect the work at his option. Work determined by the Owner not to meet the specifications will be repaired or replaced as the Owner's option. END OF SECTION ��w ►w aMna a w•oovRa e► �o,r.V m. sm RKLIXX Weaver Consultants Group, LLC 13120 -Page 3 of 3 DIVISION 15 MECHANICAL SECTION 1S200 PIPELINES, AIR, LIQUID, VACUUM PART 1 GENERAL 1.1 REFERENCES The publications listed below form part of this specification to the extent referenced. The publications are referred to within the text by basic designation only. ANSI 81.20.11998 ANSI B16.31998 ASME B1.20.1 ASTM A153 ASTM B88 ASTM D 2774 ASTM D 33SO ASTM D 1693 ASTM D 2837 ASTM F 412 PART 2 PRODUCTS 2.1 PIPING SYSTEMS 2.1.1 Compressed Air Pipe Threads, General Purpose Malleable Iron Threaded Fittings Pipe Threads, General Purpose Specification for Zinc Coating (Hot -Dip) on Iron and Steel Hardware Standard Specification for Seamless Copper Water Tube Recommended Practice for Underground Installation of Thermoplastic Pressure Piping. Polyethylene Plastics Pipe and Fitting Materials Environmental Stress -Cracking of Ethylene Thread. Obtaining Hydrostatic Design Basis for Thermoplastic Pipe Materials Definitions of Terms Relating to Plastic Pipe Systems. All piping systems and their component parts which are installed to carry air at more than atmospheric pressure shall be of adequate design and strength to safely withstand pressures to be placed upon them without the resulting stresses exceeding the allowable stress for the material used in their construction. The allowable stresses to be used shall be determined by referring to recognized standards for material and design as developed by the ANSI. The only non-metallic pipe acceptable for pressure line service with gaseous substances is that which is listed by its manufacturer as adequate to withstand design pressures. Nylon is the only acceptable plastic resin for compressed air transmission tubing, and then only up to 3/8-inch outside diameter. All elements of any compressed air system are to be manufacturer rated to at least 180 prig. Compressed air pipe to be ASTM Schedule 40, hot -dipped galvanized, ANSI 81.20.1, couplings and unions Class 150 +�twear+�a�rvr.�a�unnx c�a r �o.-0o►a+ou tuvoocsuszoo►.rursanuac�oa Weaver ConsutentsGroup, LLC 15200 -Page 1 of 3 (minimum), or seamless copper tube, type K or L, ASTM 888, soldered joined, or Nylon 6, or Nylon 11(up to 3/8-Inch outside diameter). 2.1.2 Liquid All piping systems and their component parts that are installed to carry liquid, including contaminated groundwater, shall be of adequate design and strength to safely withstand pressures to be placed upon them without the resulting stresses exceeding the allowable stress for the material used in their construction. The allowable stresses to be used shall be determined by referring to applicable manufactures ratings. Acceptable materials for liquid transmission lines (i.e., water, contaminated water, or petroleum) include the following: High density polyethylene (HDPE), Type 3048 or Type 4710 resins Nylon 6, Nylon 11 Polyvinyl chloride, ASTM Schedule 40 (or higher) 2.1.3 Vacuum All piping systems and their component parts that are installed to convey vacuum shall be of adequate design and strength to safely withstand vacuum or pressures to be placed upon them without the resulting stresses exceeding the allowable stress for the material used in their construction. The allowable stresses to be used shall be determined by referring to applicable manufactures ratings. Acceptable materials will include: High density polyethylene (HDPE), Type 3048 or Type 4710 resins. Polyvinyl chloride, ASTM Schedule 40 (or higher) 2.2 FITTINGS AND JOINTS Acceptable fittings and joints will include the fallowing: Threaded galvanized pipe: ANSI 81.20.1, couplings, flanges, or and unions Class 150 (minimum) Seamless copper tube type K or L: ASTM B88, solder joined HDPE: Fusion butt welded if field, fusion -welded if shop fabricated Plastic resin tubing: Brass, plated bass, or stainless steel instant tube fittings. Compression fittings shall not be incorporated into the work except for shop fabricated control systems fully tested and verified leak -free prior to delivery 2.3 VALVES Manual control valves to be brass, with threaded or soldered connections: K:1WD61Lf{CllEllfMIfAATbM�90079�15110t00lMIWMAN�CAMDOCSy153DONIFLN�SAptLQUW000 Weaver Consultants Group, LLC 15200 -Page 2 of 3 Maximum Pressure: W.O.G. (water, oil, inert gas): 1/4" to 2": 600 psi @ 100' F, 21/2" to 4": 450 psi @ 100° F, W.S.P. (working steam pressure): 150 psi @ 366' F Vacuum Rating: 29.92" Hg Temp. Range: Threaded: -40° to +366' F PUMP TUBING Air supply and exhaust tubing: 3/8-inch OD Nylon 11, 0.050-in wall thickness Product Discharge tubing: %-inch OD Nylon 11, 0.062-in wall thickness HDPE pipe: Pipe to be flexible HDPE,1.38-in ID,1.572-in OD 2.4 PRESSURE/VACUUM GAUGES Shall be manufactured expressly for their intended service. PART 3 EXECUTION 3.1 GENERAL All work is to conform to applicable standards. Pipe and valve work is to be adequately supported and braced. Threaded joints are to be made using appropriate thread sealing compounds. 3.2 CONTINUITY Air and liquid lines shall be comprised of the longest possible continuous lengths so as to minimize the need for joints, couplings, or connections. 3.3 FLOW METER(S) In -line mechanical flow meter(s) will be installed upstream from system elements altering water chemistry, such as air strippers. END OF SECTION +c1►�rer�uyaxrrrwsaiau we.00l AWAC"DOCS05MPPMAWAoRLKMDW Weawr Consultants Group, LLC 15200 - Page 3 of 3 DIVISION 16 ELECTRICAL SECTION 16050 BASIC MATERIALS AND METHODS PART 1 GENERAL 1.1 REFERENCES The publications listed below form part of this specification to the extent referenced. The publications are referred to within the text by basic designation only. IEEE C2 (2005) National Electrical Safety Code NFPA 70 (2005) National Electrical Code NEMA 250 (2003) Enclosures for Electrical Equipment (1,000 Volts Maximum) 1.2 ELECTRICAL CHARACTERISTICS Electrical characteristics for this project shall be 480 volts primary, three phase, four wire, and 240/120 volts primary, single phase, three wire. Characteristics of primary service to be provided by the Owner are to be verified with facility personnel. 1.3 POSTED OPERATING INSTRUCTIONS Provide for each system and principal item of equipment as specified in the technical sections for use by operation and maintenance personnel. The operating instructions shall include the following: a. Wiring Diagrams, control diagrams, and control sequence for each principal system and item of equipment. b. Start up, proper adjustment, operating, lubrication, and shutdown procedures. c. Safety precautions. d. The procedure in the event of equipment failure. e. Other items of Instruction as recommended by the manufacturer of each system or item of equipment. Print or engrave operating instructions and frame under glass or in approved laminated plastic. Post instructions where directed. For operating instructions exposed to the weather, provide weather -resistant materials or weatherproof enclosures. Operating instructions shall not fade when exposed to sunlight and shall be secured to prevent easy removal or peeling. 1.4 ELECTRICAL REQUIREMENTS Electrical installations shall conform to IEEE C2, NFPA 70, and requirements specified herein. Electrical installations in areas that may develop hazardous atmospheres during abnormal operation, such as during leaks of petroleum vapors, water, or liquid phase petroleum, shall be suitable for use in ANSI/NFPA Class I, Div. 2, Group D areas. r�www+►wevrwrow�unaw��oo- r w�oovaarrauv�uuevooausasoEc, 4T A*n a j= Weaver Consultants Group, LLC 16050 -Page 1 of 2 PART 2 PRODUCTS 2.1 FACTORY APPLIED FINISH Electrical equipment shall have factory -applied painting systems which shall, as a minimum, meet the requirements of NEMA 250 corrosion -resistance test and the additional requirements specified in the technical sections. Electrical installations in areas that may develop hazardous atmospheres during abnormal operation, such as during leaks of petroleum vapors, water, or liquid phase petroleum, shall be suitable for use in ANSI/NFPA Class 1, Div. 2, Group D areas. PART 3 EXECUTION Not Applicable. END OF SECTION c�wse►ew�vrr�auw w+onlvieca.aMrwerooauw�osSUT A07HDMDW Weaver Consultan s Group, LLC 16050 -Page 2 of 2 SECTION 16402 INTERIOR DISTRIBUTION SYSTEM PART 1 GENERAL 1.1 REFERENCES The publications listed below form part of this specification to the extent referenced. The publications are referred to within the text by basic designation only. NFPA 70 (2005) National Electrical Code NEMA C80.1, UL 6 (1994) Rigid Steel Conduit —Zinc Coated (GRC) UL 1242 (2000, Rev thru Jun 2002) General -Use Snap Switches NEMA RN 1 (2005) Polyvinyl Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit UL 1 (2005) Flexible Metal Conduit UL 514B (20D4) Conduit, Tubing and Cable Fittings UL 50 (1995; Rev thru Sep 2003) Enclosures for Electrical Equipment UL 83 (2005e13) Thermoplastic -Insulated Wires and Cables UL 44 (2005) Thermoset -insulated Wires and Cables ASTM B 1 (2001) Hard -Drawn Copper Wire ASTM B 8 (2004) Concentric -Lay -Stranded Copper Conductors, Hard, Medium - Hard, or Soft UL 854 (2004) Service -Entrance Cables UL 486A-4868 (2003, Rev thru Apr 2004) Wire Connectors NEMA WD 1 (1999) General Color Requirements for Wiring Devices UL 20 (2000; Rev thru Jun 20D2) General -Use Snap Switches NEMA KS 1 (2001) Enclosed and Miscellaneous Distribution Equipment Switches (600 volts maximum) UL 498 (2001; Rev thru Oct 2002) Attachment Plugs and Receptacles UL 489 (2002; Rev thru May 2003) Molded -Case Circuit Breakers, Molded -Case Switches, and Circuit -Breaker Enclosures UL 467 (2004) Grounding and Bonding Equipment c1we�►ncx ra arwar as l�n uw+on�nn+A«enru.mcsusraa►�o TSVIDW Weaver Consultants Group, LLC 16402 -Page 1 of 7 IEEE C2 (2005) National Electrical Safety Code NFPA 780 (2004) Installation of Lighting Protection Systems IEEE Std 81 (1983) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface potentials of a Ground System (Part 1) Normal Measurements PART 2 PRODUCTS 2.1 MATERIALS AND EQUIPMENT Materials, equipment, and devices shall, as a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70. Electrical materials and equipment in areas that may develop hazardous atmospheres during abnormal operation, such as during leaks of petroleum vapors, water, or liquid phase petroleum, shall be suitable for use in ANSI/NFPA Gass I, Div. 2, Group D areas. 2.2 CONDUIT AND FITTINGS Shall conform to the following: 2.2.1 Rigid Metallic Conduit 2.2.1.1 Rigid, Threaded Zinc -Coated Steel Conduit NEMA C 80.1, U1.6. 2.2.2 Intermediate Metal Conduit CIMC) U11242, zinc -coated steel only. 2.2.3 Plastic -Coated Rigid Steel and 1MC Conduit NEMA RN 1, Type 40 (40 mils thick). 2.2.4 Flexible Metal Conduit UL 1. 2.2.5 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit UL 514B. Ferrous fittings shall be cadmium- or zinc -coated in accordance with UL 514B. 2.3 CABINETS, JUNCTION BOXES, AND PULL BOXES Volume greater than 100 cubic inches, UL 50, hot -dip, zinc -coated, if sheet steel. �+ ►•+Fcw.0 losaolwinr Ma�►aocrits ,MWT..SIUM Weaver Consultants Group, LLC 16402 - Page 2 of 7 2.4 WIRES AND CABLES Wires and cables shall meet applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. 2.4.1 Conductors Conductors No. 8 AWG and larger diameter shall be stranded. Conductors No. 10 AWG and smaller diameter shall be solid, except that conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3, shall be stranded unless specifically indicated otherwise. Conductor sizes and ampacities shown are based on copper. All conductors shall be copper. 2A.1.1 Equipment Manufacturer Requirements When manufacturer's equipment requires copper conductors at the terminations or requires copper conductors to be provided between components of equipment, provide copper conductors or splices, splice boxes, and other work required to satisfy manufacturer's requirements. 2.4.2 Color Coding Provide for service, feeder, branch, control, and signaling circuit conductors. Color shall be green for grounding conductors and white for neutrals; except where neutrals of more than one system are installed in the same raceway or box, other neutrals shall be white with a different colored (not green) stripe for each. Color of ungrounded conductors in different voltage systems shall be as follows: a. 120/240 volt, single phase: Black and red 2.4.3 Insulation Unless specified or indicated otherwise or required by NFPA 70, power and lighting wires shall be 600- volt, Type THWN/THHN conforming to UL 83 or Type XHHW or RHW conforming to UL 44, except that grounding wire may be type TW conforming to UL 83; remote -control and signal circuits shall be Type TW or TF, conforming to UL 83. Where lighting fixtures require 90-degree Centigrade (C) conductors, provide only conductors with 90-degree C insulation or better. 2.4.4 Bonding Conductors ASTM B 1, solid bare copper wire for sizes No. 8 AWG and smaller diameter; ASTM B 8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter. 2.4.5 Service Entrance Cables Service Entrance (SE) and Underground Service Entrance (USE) Cables, UL 854. ti+vs arevr as no ru�o �s�w«ona�auwWy�woocsue+a�n� Wr.smwc Weaver Consultants Group, LLC 16402 -Page 3 of 7 2.5 SPLICES AND TERMINATION COMPONENTS UL 486A-486B for wire connectors and UL 510 for insulating tapes. Connectors for No. 10 AWG and smaller diameter wires shall be insulated, pressure -type in accordance with UL 486A-4866 or UL 486C (twist -on splicing connector). Provide solderless terminal lugs on stranded conductors. 2.6 DEVICE PLATES Provide UL listed, one-piece device plates for outlets to suit the devices installed. For metal outlet boxes, plates on unfinished walls shall be of zinc -coated sheet steel or cast metal having round or beveled edges. For nonmetallic boxes and fittings, other suitable plates may be provided. Plates on finished walls shall be nylon or lexan, minimum 0.03 inch wall thickness. Plates shall be same color as receptacle or toggle switch with which they are mounted. Screws shall be machine -type with countersunk heads in color to match finish of plate. 2.7 SWITCHES 2.7.1 Toggle Switches NEMA WD 1, UL 20, single pole, totally enclosed with bodies of thermoplastic or thermoset plastic and mounting strap with grounding screw. Handles shall be white thermoplastic. Wiring terminals shall be screw -type, side -wired or of the solderless pressure type having suitable conductor -release arrangement. 2.7.2 Disconnect Switches NEMA KS 1. 2.8 RECEPTACLES U1.498, hard use, heavy-duty, grounding -type. 2.9 GROUNDING AND BONDING EQUIPMENT 2.9.1 Ground Rods UL 467. Ground rods shall be copper -clad steel, with minimum diameter of Y inch and minimum length of 10 feet. PART 3 EXECUTION 3.1 INSTALLATION 3.1.1 Underground Service Underground service conductors and associated conduit shall be continuous. Ktwemula cwra�awsu aemlvAw�uhuRrcoausoo�ixasr MDOC Weaver Consultants Group, LLC 16402 - Page 4 of 7 3.1.2 Service Entrance Identification Service entrance disconnect devices, switches, and enclosures shall be labeled and identified as such. 3.1.3 Wiring Methods Provide Insulated conductors installed in rigid steel conduit, IMC, rigid nonmetallic conduit, or EMT, except where specifically indicated or specified otherwise or required by NFPA 70 to be installed otherwise. Grounding conductor shall be separate from electrical system neutral conductor. Provide insulated green equipment grounding conductor for circuit (s) installed in conduit and raceways. Minimum conduit size shall be % inch in diameter for low voltage fighting and power circuits. 3.1.4 Conduit Installation 3.1.4.1 Conduit Support Support conduit by pipe straps, wall brackets, hangers, or ceiling trapeze. Fasten by wood screws to wood; by toggle bolts on hollow masonry units; by concrete inserts or expansion bolts on concrete or brick; and by machine screws, welded threaded studs, or spring -tension clamps on steel work. Threaded C-clamps may be used on rigid steel conduit only. 3.1.4.2 Directional Changes in Conduit Runs Make changes in direction of runs with symmetrical bends or cast -metal fittings. Make field -made bends and offsets with hickey or conduit -bending machine. Do not install crushed or deformed conduits. Avoid trapped conduits. Prevent plaster, dirt, or trash from lodging in conduits, boxes, fittings, and equipment during construction. Free clogged conduits of obstructions. 3.1.4.3 Flexible Connections Provide flexible steel conduit between 3 and 6 feet in length for recessed and semirecessed lighting fixtures; for equipment subject to vibration, noise transmission, or movement; and for motors. Install flexible conduit to allow 20 percent slack. 3.1.5 Boxes, Outlets, and Supports Provide boxes in wiring and raceway systems wherever required for pulling of wires, making connections, and mounting of devices or fixtures. Boxes for metallic raceways shall be cast -metal, hub - type when located in wet locations, when surface mounted on outside of exterior surfaces, and when specifically indicated. Boxes in other locations shall be sheet steel, except that aluminum boxes may be used with aluminum conduit, and nonmetallic boxes may be used with nonmetallic sheathed cable conduit system. Each box shall have volume required by NFPA 70 for number of conductors enclosed in box. Boxes for mounting lighting fixtures shall be minimum 4 inches square, or octagonal, except that smaller boxes may be installed as required by fixture configurations, as approved. irtw,&aWw*nu t O-W%FF" UUACAV DOUU6= R Wr.SK" Weaver Consultants Group, LLC 16402 - Page 5 of 7 3.1.5.1 Pull Boxes Construct of at least minimum site required by NFPA 70 except where cast -metal boxes are required in locations specified herein. Provide boxes with screw -fastened covers. Where several feeders pass through common pull box, tag feeders to indicate clearly electrical characteristics, circuit number, and panel designation. 3.1.6 Conductor Identification Provide conductor identification within each enclosure where tap, splice, or termination is made. For conductors No. 6 AWG and smaller diameter, color coding shall be by factory -applied, color - impregnated insulation. For conductors No. 4 AWG and larger diameter, color coding shall be by plastic -coated, self --sticking markers; colored nylon cable ties and plates; or heat shrink -type sleeves. 3.1.7 Splices Make splices in accessible locations. Make splices in conductors No.10 AWG and smaller diameter with insulated, pressure -type connector. Make splices in conductors No. 8 AWG and larger diameter with solderless connector, and cover with insulation material equivalent to conductor insulation. 3.1.8 Grounding and Bonding Provide in accordance with NFPA 70 and NFPA 780. 3.1.8.1 Ground Rods Provide cone pointed ground rods. The resistance to ground shall be measured using the fall -of - potential method described in IEE Std 81. The maximum resistance of a driven ground shall not exceed 25 ohms under normally dry conditions. If this resistance cannot be obtained with a single rod, additional rods shall be installed at least 6 feet apart. In high -ground -resistance, UL listed chemically charged ground rods may be used. If the resultant resistance exceeds 25 ohms measured not less than 48 hours after rainfall, notify the Engineer who will decide on the number of ground rods to add. 3.1.8.2 Resistance Maximum resistance -to -ground of grounding system shall not exceed 25 ohms under dry conditions. Where resistance obtained exceeds 25 ohms, contact Engineer for further instructions. 3.1.9 600-Volt Wiring Test Test wiring rated 600 volt and less to verify that no short circuits or accidental grounds exist. Perform insulation resistance tests on wiring No. 6 AWG and larger diameter using instrument which applies voltage of approximately 500 volts to provide direct reading of resistance. Minimum resistance shall be 250,000 ohms. ..,rwaOMU"MA Mr.s xooc Weaver consultants Group, LLC 16402 - Page 6 of 7 3.1.10 Ground -Fault Receptacle Test Test ground -fault receptacles with a "load" (such as a plug in light) to verify that the "line" and "load" leads are not reversed. 3.1.11 Grounding System Test Test grounding system to ensure continuity, and that resistance to ground is not excessive. Test each ground rod for resistance to ground before making connections to rod; tie grounding system together and test for resistance to ground. Make resistance measurements in dry weather, not earlier than 48 hours after rainfall. Submit written results of each test to Engineer, and indicate location of rods as well as resistance and soil conditions at time measurements were made. END OF SECTION caws a,�r„waa�a„u on�oo , s,lo�ool►aar,N��rur,mcsus�a Mr. SMOM Weaver Consultants Group, LLC 16402 -Page 7 of 7 SECTION 16446 PANELBOARDS PART 1 GENERAL 1.1 REFERENCES The publications listed below form part of this specification to the extent referenced. The publications are referred to within the text by basic designation only. NEMA 250 (2003) Enclosures for Electrical Equipment (1,000 Volts Maximum) NEMA PB 1 (2000; R 2001) Standard for Panelboards NEMA AB 1 (2002) Molded -Case Circuit Breakers, Molded Case Switches, Circuit - Breaker Enclosures, and Accessory High -Fault Protectors 1.2 GENERAL REQUIREMENTS Section 16050 BASIC MATERIALS AND METHODS applies to work specified In this section. PART 2 PRODUCTS 2.1 PANELBOARDS Exterior panels, such as remote disconnect, shall conform to NEMA 4X, Square D or approved equal. Interior power -distribution panelboards and lighting and appliance branch -circuit panelboards shall be totally enclosed in a steel cabinet, dead -front circuit breaker type with copper buses, surface- or flush - mounted as indicated. Panelboards shall conform to NEMA PB 1, Square D or approved equal, or NEMA 7 if installed in areas that may develop hazardous atmospheres during abnormal operation, such as during leaks of petroleum vapors, water, or liquid phase petroleum. 2.2 CIRCUIT BREAKERS Circuit breakers shall be Square D or approved equal. Frame and trip ratings shall be appropriate for loads on each circuit. PART 3 EXECUTION 3.1 INSTALLATION Panelboards shall be installed as Indicated and in accordance with the manufacturer's instructions. Panels shall be fully aligned and mounted so that the height of the top operating handle will not exceed 72 inches above the finished floor. cu�ar�nrrrnom�oo-rw�o,.wMOWnoocsusv�ws,w�evsax Weaver Consuhants Group, LLC 16446 -Page 1 of 2 3.2 SITE TESTING Panelboards shall be given continuity and insulation tests after the installation has been completed and before the panelboard is energized. Insulation tests on panelboards rated 300 volts or less shall be conducted using a 500-volt minimum Insulation -resistance test set. Readings shall be recorded after i minute and until the reading is constant for 15 seconds. Resistance between phase conductors and between phase conductors and ground shall be not less than 25 megohms. Insulation tests on 480-volt panelboards shall be conducted using a 1,000-volt insulation -resistance test. Reading shall be recorded every minute until three equal and consecutive readings have been obtained. Resistance between phase conductors and between phase conductors and ground shall be not less than 50 megaohms. Test data shall be recorded and shall include the location and identification of panelboards and megohm readings versus time. END OF SECTION K:�wec, a,err,nr�oau��l�,st �o�oo�wro,MWICWDO 64"PA KWAWI a Weaver Consultants Group, LLC 16446 -Page 2 of 2 SECTION 16510 INTERIOR LIGHTING PART 1 GENERAL 1.1 REFERENCES The publications listed below form part of this specification to the extent referenced. The publications are referred to within the text by basic designation only. UL 1598 (2004) Luminaires UL 935 (2001) Fluorescent -Lamp Ballasts NEMA C82.11 (2002) High -Frequency Fluorescent Lamp Ballasts NFPA 70 (2005) National Electrical Code IEEE C2 (2005) National Electrical Safety Code 1.2 RELATED REQUIREMENTS Materials not considered to be lighting equipment or lighting fixture accessories are specified in Section 16402 INTERIOR DISTRIBUTION SYSTEM. PART 2 PRODUCTS 2.1 FLUORESCENT LIGHTING FIXTURES UL 1598. Fluorescent fixtures shall have electronic ballasts unless specifically indicated otherwise. 2.1.1 Fluorescent Lamp Electronic Ballasts The electronic ballast shall as a minimum meet the following characteristics: a. Ballast shall comply with UL 935, NEMA C82.11, and NFPA 70 unless specified otherwise. Ballast shall be 100% electronic high frequency type with no magnetic core and coil components. Ballast shall be designed for the wattage of the lamps used in the indicated application. Ballasts shall be designed to operate on the voltage system to which they are connected. b. Ballast shall be capable of starting and maintaining operation at a minimum of 0 degrees F unless otherwise indicated. 2.1.1.1 T-8 Lamp Ballast Input wattage: 62 watts (maximum) when operating two F32T8 lamps. 2.1.2 Fluorescent Lamps T-8 rapid start lamps shall be rated 32 watts (maximum) and color temperature falling within the range of 2700 K to 3500 K. .r�wee ae�xr s,w�aaa►a WNIOWDOMMUOMr: UWrNGWC Weaver Consultants Group, LLC 16510 -Page 1 of 2 2.2 RECESS- AND FLUSH -MOUNTED FIXTURES Provide type that can be relamped from the bottom. Access to ballast shall be from the bottom. PART 3 EXECUTION 3.1 INSTALLATION Electrical installations shall conform to IEEE C2, NFPA 70, and to the requirements specified herein. 3.1.1 Lamps Lamps of the type, wattage, and voltage rating indicated shall be delivered to the project in the original cartons and installed just prior to project completion. 3.1.2 Lighting Fixtures Set lighting fixtures plumb, square, and level with ceiling and walls, in alignment with adjacent lighting fixtures, and secure in accordance with manufacturers' directions and approved drawings. Installation shall meet requirements of NFPA 70. END OF SECTION raw aewr,hwarw wsoalv�aK4WJC"WOUMOW LGH ro" Weaver Consultants Group, LLC 16510 - Page 2 of 2 APPENDIX APPROVED SITE INVESTIGATION/REMEDIATION WORK PLAN SECTION 00800 SUPPLEMENTARY CONDITIONS PART 1 GENERAL 1.1 CONTRACT REQUIREMENTS This Supplementary Conditions (SC) amend or supplement the Standard General Conditions of the Construction Contract (EJCDC C-700, 2b07 Edition) and other provisions of the Contract Documents as Indicated below. All provisions which are not so amended or supplemented remain in full force and effect. SC-1 The terms used in these Supplementary Conditions, which are defined in the Standard General Conditions of the Construction Contract (EJCDC C-700, 2007 Edition) have the meanings assigned to them in the General Conditions. SC-2.01.E Within 20 days after the Effective Date of the Agreement, but before any Work at the site is started, contractor shall deliver to Owner, with a copy to Engineer, certificates and other evidence of insurance requested by Owner which Contractor is required to purchase and maintain in accordance with paragraphs 5.03 through 5.06 of the General conditions, as amended in theses Supplementary Conditions. SC-2.03 The Contractor shall complete, in an acceptable manner, all of the work contracted for in the time stated herein. Computation of Contract Time shall commence on the start date given in the Notice to Proceed, and every calendar day following, except herein proved, shall be counted as Contracted Time, in accordance with Paragraph 17.02 SC-4.02.A In the preparation of drawings and specifications, the Engineer has relied upon the subsurface boring and testing information contained in the Appendix C of the approved Site Investigation/Remediation Work Plan (51/RWP) dated September 16, 2013. SC-4.02.8 Information and data reflected In the Contract Documents with respect to existing structures and facilities at or contiguous to the site are based upon information obtained by requesting underground utility locates and surveying of the resulting marks. Neither the Owner nor the Engineer warrants their accuracy or completeness. CONTRACTOR'S LIABILITY INSURANCE: SC-5.04 The limits of liability for the insurance required by paragraph 5.04 of the General Conditions shall provide coverage for not less than the following amounts or greater where required by Laws or Regulations: 5.04A.1 and 5.04.A.2 Worker's Compensation, etc., under paragraphs 5.04A.1 and 5.04A.2 of the General Conditions- (1) State Statutory (2) Employers Liability Statutory ctwe�nmr�vr no ao t t�vrnisswsootrxar�unuRroocswoennwr mAomc Weaver Consultants Group, LLC 00800 - Page 1 of 7 5.04.A.3, 5.04.A.4, 5.04A5 and 5.04A.6 Comprehensive General Liability (under paragraphs 5.04A.3, through 5.04.A.6 of the General Conditions): (1) General Liability: $2,000,000 General Aggregate $2,000,000 Products — Comp/Op Aggregate $1,000,000 Each Occurrence $ 50,000 Fire Damage (any one fire) $ 5,000 Medical Expense (anyone person) (2) Property Damage Liability Insurance will provide Explosion, Collapse, and Underground coverages, where applicable. (3) Personal Injury with employment exclusion deleted. $1,000,000 Annual Aggregate 5.04A6 Comprehensive Automobile Liability: Combined Single Limit (CSL): $1,000,000 Each Occurrence 5.04A7 Excess Liability insurance shall provide umbrella coverage for both Comprehensive General Liability (paragraphs GC-5.04A3 through GC 5.04A.5) and Comprehensive Automobile Liability (paragraph GC-5.04A6) with a minimum limit of $5,000,000. OWNER'S LIABILITY INSURANCE: SC-5.05 The Contractor, under paragraphs GC-5.02, 5.03 and 5.04, shall provide such contractual coverage suffidentiy broad to insure the Owner, the Engineer, their consultants, and each of their officers, agents, and employees as additional insured under the comprehensive general liability insurance required. CONCERNING SUBCONTRACTOR;, SUPPLIERS, AND OTHERS: SC-6.06.8 As part of the BID or the PROPOSAL, the Owner shall require the identity of the Contractor's proposed Subcontractors and Suppliers of Equipment or Materials in order to better evaluate the proposal or bid. In the instance where identification of Suppliers is required, supply only one name per equipment or material item. r�w�w►aexrwra�aanow co- r�t3sswaoclP�.wYl�aa►noatansoowr wwmc Weaver Consultants Group, LLC 00800 -Page 2 of 7 PERMITS: SC-6.08 Responsibility for obtaining permits shall be as described in Section 01010, Summary of Work. All other requirements of paragraph 6.08 of the General Conditions still apply to the Contract Documents. �� SC-6.10 Contractor shall apply for Exemption for Sales Tax (if applicable). INDEMNIFICATION: SC-6.20A The Contractor and Subcontractor (hereinafter "Indemnitors") hereby agree to indemnify, save and hold harmless, and defend at its own expense of the Owner and Engineer, their respective partners, agents, employees, and any other person or entity for whom any of them may be legally responsible (herein collectively called "Indemnities") against all claims, losses, damages, suits, costs and expenses, including attomeys' fees, or actions of any nature whatsoever which arise out of the work to be performed by the Indemnitor, including without limiting the generality of the foregoing, all liability for claims for death or damage to property, including the loss or use thereof and consequential damages therefrom, or damages for economic loss to any Indemnitee or indemnitor or its employees, servants and agents whether based upon, or claimed to be based upon, statutory, contractual, tort, or other liability of any indemnitee caused or alleged to be caused by the joint, or several, or comparative (but not sole) negligence, breach of contract, breach of warranty, strict liability, or other breach of duty by any Indemnitee. If any part of this provision id adjudged to be contrary to law, the remaining parts of the provision shall in all other respects be and remain legally effective and binding. Moreover, this provision shall not be construed to eliminate or in any way reduce any other indemnification or other right which the Owner or the Engineer has by law. COORDINATION: SC-7.02 When the Owner contracts with others for performance of other work on the Project at the site, the Owner will identify a construction coordinator who will have authority and responsibility for coordination of the activities among the various prime contractors' work at the site. PROJECT REPRESENTATION: SC-9.03A The following is a listing of the "Duties, Responsibilities, and limitations of Authority of Resident Project Representative" and supplements paragraph 9.03A of the General Conditions: DUTIES, RESPONSIBILITIES, AND LIMITATIONS OF THE AUTHORITY OF THE RESIDENT PROJECT REPRESENTATIVE A. GENERAL: The Resident Project Representative is the Engineer's Agent and shall act under the supervision and direction of the Engineer. He shall confer with the Engineer regarding his actions and shall generally communicate with the Owner only through the Engineer. c1ws arerr�wauna ao- sa+ouwrou mcwooawoeoosu..COMMC Weaver Consultants Group,LLC OMM -Page 3 of 7 B. DUTIES AND RESPONSIBILITIES: The Resident Project Representative shall: 1. Schedule: Review the progress schedule prepared by the Contractor for compliance with the contract and give written advice to the Engineer concerning its acceptability. 2. Conferences: Attend pre -construction conferences. Arrange a schedule of progress meetings and other job conferences as required in consultation with the Engineer and notify those expected to attend in advance. Maintain and circulate copies of records of the meetings. 3. liaison: Serve as the Engineer's liaison with the Contractor working principally through the Contractor's superintendent. Alert the Contractor, through his superintendent, to the hazards involved in accepting and acting upon instructions form the Owner or others, except such instructions transmitted through the Engineer. a. Assist the Engineer in obtaining from the Owner additional details or information, when required, at the job site for proper execution of the work. 4. Approvals: Assist the Engineer in obtaining from the Contractor a list of his proposed supplies and subcontractors. 5. Samples: Assist the Engineer in obtaining field samples of materials delivered to the site which are required to be furnished, and keep record of actions taken by Engineer. 6. Shop Drawings: a. Receive approved shop drawings and other submissions from the Engineer; record data received, maintain a file of the drawings and submissions, and check for construction for compliance with them. b. Alert the Contractor's superintendent when he observes materials or equipment being installed before approval of shop drawings or samples, where such are required, and advise the Engineer when he believes it is necessary to disapprove work as failing to conform to the Contract Documents. 7. Review of Work, Inspections, and Tests: Conduct on -site observations of the work in progress for the Engineer as a basis for determining that the Project is proceeding in accordance with the Contract Documents, and report to the Engineer whenever he believes that any work should be rejected or specialty tested, or that the work should be stopped to ensure that the completed Project will comply with the requirements of the Contract Documents. a. Verify that tests, which are required by the Contract Documents are conducted and that the Contractor maintains adequate records thereof; observe, record, and report to the Engineer appropriate details relative to the test procedures and startups. �t, wwmrr�r+a r�a��a�, „st�uy,�mv�ra,,wuv�u,caswo cosur WAV ax Weaver Consultants Group, LLC OO800 -Page 4 of 7 b. Accompany visiting inspectors representing public or other agencies having jurisdiction over the Project, record the outcome of these inspections, and report to the Engineer. S. Interpretations of Contract Documents: Transmit to the Contractor the Engineer's interpretations of the Contract Documents. 9. Modifications: Consider and evaluate Contractor's suggestions for modifications in drawings or specifications and reports them with recommendations to the Engineer. 10. Records: Maintain at the job site orderly files for correspondence, report of job conferences, shop drawings, and other submissions, reproductions of original Contract Documents including all addenda, change orders, field orders, and additional drawings issued subsequent to the award of the contract, the Engineer's interpretations of the Contract Documents, progress reports, and other Project related documents. a. Keep a diary, log book, or daily report recording hours on the job site, weather conditions in general, and specific observations in more detail as in the case of observing test procedures. b. Record names, addresses, and telephone numbers of all Contractors, subcontractors, and major material suppliers. C. Maintain a set of drawings on which authorized changes are noted and deliver to the Engineer at the completion of the Project. 11. Reports: Furnish the Engineer periodic reports, as required, of progress of the Project and the Contractor's compliance with approved progress schedule. a. Consult with the Engineer in advance of scheduled major tests, inspections, or start of important phases of the Project. 12. Payment Requisitions: Review applications for payment with the Contractor for compliance With the established procedure for their submission and forward them with recommendations to the Engineer, noting particularly their relation to the work completed and materials and equipment delivered at the site. 13. Guarantees, Certificates, Maintenance and Operation Manuals: During the course of the work, assemble Guarantees, Certificates, Maintenance and Operation Manuals, and other required data to be furnished by the Contractor, and upon acceptance of the project, deliver this material to the Engineer for his review and forwarding to the Owner. 14. Completion: Prior to inspection for substantial completion, submit to the Contractor a list of observed items requiring correction. a. Conduct final inspection in the company of the Engineer and the Owner and prepare a final list of items to be corrected. x�wer.�utc rrawauw,� u ssw+�v�arwMu+�►oocsloceocsuv COW= Weaver consultants Group, LLC 00800 - Page 5 of 7 b. Verify that all items on final list have been corrected and make recommendations to the Engineer concerning acceptance. C. LIMITATIONS OF AUTHORITY: Except upon written instructions of the Engineer, the Resident Project Representative: 1. shaft not authorize any deviation from the Contract Documents; 2. shall not undertake any of the responsibilities of the Contractor, the subcontractors, or the Contractor's superintendent. 3. shall not expedite the work for the Contractor. 4. shall not advise on or issue directions relative to any aspect of the means, methods, techniques, sequences, or procedures of construction, unless such is specifically called for in the Contract Documents. UNIT PRICE WORK: SC-11.03.D. The unit price of an item of Unit Price Work shall be subject to re-evaluation and adjustment under the following conditions: 11.03.D.1 if the total cost of a particular item of Unit Price Work amounts to 10% or more of the Contract Price and the variation in the quantity of that particular item of Unit Price Work performed by the Contractor differs by more than 25% from the estimated quantity of such item indicated in the Agreement; and 11.03.D.2 if there is no corresponding adjustment with respect to any other item of Work; and 11.03.D.3 if Engineer believes that Contractor has incurred additional expense as a result thereof; or 11.03.D.4 if Owner believes that the quantity variation entities it to an adjustment in the unit price. Either Owner or Contractor may make a claim for an adjustment in the Contract Price in accordance with Article 11 if the parties are unable to agree as to the effect of any such variations In the quantity of Unit Price Work Performed. DISPUTE RESOLUTION: 16.01.A Either Owner or Contractor, when mutually agreed to by both parties may request mediation of any Claim submitted to Engineer for a decision under Paragraph 1D.05 before such decision becomes final and binding. The mediation will be governed by the Construction Industry Mediation Rules of the American Arbitration Association in effect as of the Effective Date of the Agreement. The request for mediation shall be submitted in writing to the American Arbitration Association and the other party to the Contract Timely submission of the request shall stay the effect of Paragraph 10.05.E. � tiw,eMux�++rra�a■.��r,�uw�oo�n�a onaw w. m aoa Weaver Consultants Group, LLC 00800 -Page 6 of 7 x�w a+Exr a ioaoo��o„wwtiouvnocsloceoowv. WWAOc Weaver Consultants Group, LLC 00800 - Page 7 of 7