HomeMy Public PortalAboutRE_ Town of Gulf Stream - IMAG0680_jpg (2)
Renee Basel
From:John Zoerhof <jzoerhof@HYPOWERINC.COM>
Sent:Wednesday, March 19, 2014 10:56 AM
To:Danny Brannon; 'Lehr, John'
Cc:Cliff Spitzer; 'Owen, Jay D'
Subject:RE: Town of Gulf Stream - IMAG0680.jpg
I am looking into why they used 2 pads when there are supposed to be single duplex pads in the yard.
Thanks,
John Zoerhof
Division Manager - Power Services
-----Original Message-----
From: Danny Brannon \[mailto:DBrannon@BnGEngineers.com\]
Sent: Wednesday, March 19, 2014 10:53 AM
To: 'Lehr, John'
Cc: Cliff Spitzer; John Zoerhof; 'Owen, Jay D'
Subject: RE: Town of Gulf Stream - IMAG0680.jpg
Two pads require a space of 54" x 96", while one 3phase pad requires 60" x 80". So, for space, one is better. I
will look into what they are doing. We have some locations along Hidden Harbor road that would benefit from
the reduced depth.
Is JD the Contract Rep on this job?
Danny P. Brannon, P.E.
Brannon & Gillespie, LLC
Consulting Engineers
631 US Highway One, Suite 301
North Palm Beach, Florida 33408
Off: (561) 847-4435 Cell: (561) 307-9454
Website: www.BnGEngineers.com
-----Original Message-----
From: Lehr, John \[mailto:John.Lehr@fpl.com\]
Sent: Wednesday, March 19, 2014 10:48 AM
To: Danny Brannon
Cc: 'Cliff Spitzer'; 'John Zoerhof'; Owen, Jay D
Subject: Town of Gulf Stream - IMAG0680.jpg
Danny,
FYI .................. The job was MECA'd & issued 11 Duplex pads, but if the installation is tight, as in the past, the
2-pad configuration can work.
And, no, no shortage of concrete pads.
1
John C. Lehr, Jr.
Project Manager
FPL
(561)-845-4624
-----Original Message-----
From: Danny Brannon \[mailto:DBrannon@BnGEngineers.com\]
Sent: Wednesday, March 19, 2014 9:28 AM
To: 'John Zoerhof'
Cc: Lehr, John; 'Cliff Spitzer'
Subject: RE: IMAG0680.jpg
Do you look at the FPL Distribution Construction Standards. This setup is correct. Make sure the ground has
been compacted and that pads are level.
Make sure the leading phase is going into the lighting transformer.
John, Did you approve the contractor using two single phase pads versus the three phase pad for open delta
banks? Does FPL have a material shortage problem?
Danny P. Brannon, P.E.
Brannon & Gillespie, LLC
Consulting Engineers
631 US Highway One, Suite 301
North Palm Beach, Florida 33408
Off: (561) 847-4435 Cell: (561) 307-9454
Website: www.BnGEngineers.com
-----Original Message-----
From: John Zoerhof \[mailto:jzoerhof@HYPOWERINC.COM\]
Sent: Tuesday, March 18, 2014 4:06 PM
To: Danny Brannon (DBrannon@BnGEngineers.com)
Cc: Lehr, John; Cliff Spitzer
Subject: FW: IMAG0680.jpg
Before we get too far here, what is the set up with respect to the transformer locations? This looks to me like
the low profile will be on the left. Is that correct?
Thanks,
John Zoerhof
Division Manager - Power Services
-----Original Message-----
From: Cliff \[mailto:cliffspitzer@yahoo.com\]
Sent: Tuesday, March 18, 2014 3:30 PM
To: Cliff Spitzer; John Zoerhof
Subject: IMAG0680.jpg
2
---
This email is free from viruses and malware because avast! Antivirus protection is active.
http://www.avast.com
---
This email is free from viruses and malware because avast! Antivirus protection is active.
http://www.avast.com
3