HomeMy Public PortalAboutService Update 9_11_14
Renee Basel
From:John Zoerhof <jzoerhof@HYPOWERINC.COM>
Sent:Thursday, September 11, 2014 4:11 PM
To:Danny Brannon
Cc:Cliff Spitzer; Enrique Alvarez; John Lehr; Wayne Wilson
Subject:Service Update 9/11/14
Attachments:Switching request; 20140911100618386.pdf
Importance:High
FPL Services that were converted to the new underground system on Wednesday 9-3-2014:
998 Pelican (West Service)
996 Pelican
12 Driftwood
FPL Services converted to the new underground system on Thursday 9-4-2014:
1302 Pelican
555 Pelican
2002 Pelican
2 Driftwood
FPL Services converted to the new underground system on Friday 9-5-2014:
2525 Pelican
2002 Pelican
No Outages over weekend ( Prep Work only)
Services converted to the new underground system on Monday 9/8/2014
11 Driftwood
6 Driftwood
5 Driftwood
7 Driftwood
Services converted to the new underground system on Tuesday 9/9/2014
9 Driftwood
10 Driftwood
1
1 Driftwood
4 Driftwood
8 Driftwood
Services converted to the new underground system on Tuesday 9/10/2014
998 Pelican (East)
1010 Ocean
1008 Ocean
925 Ocean (West Tennis Bldg)
Services scheduled to be converted to the new underground system on Tuesday 9/11/2014
1120 Ocean
1122 Ocean
Services scheduled to be converted to the new underground system on Tuesday 9/12/2014
925 Ocean (East Tennis Bldg)
Preparatory work to be performed 9/12 & 9/13 @ 1040, 1060, 1080, 1100 & 1111
Danny, we are having difficulty getting a proper loop switching permit for this project. They continue to
submit extensive switching orders that do not take into account work require to transfer existing facilities as
we go along the primary. (I have attached the latest order here as well as an explanation email sent by JHV)
We have asked numerous times for a Loop Permit and have gotten John Lehr involved to see if he can help.
This is going to prohibit the project from moving forward with energizations until it can be resolved
,
Regards
John Zoerhof
Division Manager – Power Services
Direct 954.917.1439
Cell 954.448.0369
954.978.9300 – Main 954.978.8666. - Fax
Please consider the environment before printing this e-mail
NOTICE: This email is intended solely for the use of the individual to whom it is addressed and may contain information that is privileged, confidential or otherwise exempt
from disclosure. If the reader of this email is not the intended recipient or the employee or agent responsible for delivering the message to the intended recipient, you are
2
hereby notified that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this communication in error, please immediately
notify us by telephone and return the original message to us at the listed email address. Thank You.
From: John Zoerhof
Sent: Tuesday, September 09, 2014 2:17 PM
To: Danny Brannon
Cc: Cliff Spitzer; Enrique Alvarez; John Lehr; Wayne Wilson
Subject:
FPL Services that were converted to the new underground system on Wednesday 9-3-2014:
998 Pelican (West Service)
996 Pelican
12 Driftwood
FPL Services converted to the new underground system on Thursday 9-4-2014:
1302 Pelican
555 Pelican
2002 Pelican
2 Driftwood
FPL Services converted to the new underground system on Friday 9-5-2014:
2525 Pelican
2002 Pelican
No Outages over weekend ( Prep Work only)
Servicesconverted to the new underground system on Monday 9/8/2014
11 Driftwood
6 Driftwood
5 Driftwood
7 Driftwood
Services converted to the new underground system on Tuesday 9/9/2014
9 Driftwood
10 Driftwood
1 Driftwood
4 Driftwood
8 Driftwood
3
Services scheduled to be converted to the new underground system on Tuesday 9/10/2014
998 Pelican (East)
1010 Ocean
1008 Ocean
925 Ocean
Services scheduled to be converted to the new underground system on Tuesday 9/11/2014
Tennis Building
1120 Ocean
1122 Ocean
This will complete the present loop section.
Switching order requested for the next loop section 9/5/14
John Zoerhof, Hypower, Inc.
Sent from my Smartphone, please disregard typos or grammatical errors
4
Switching Order: 40727-A-14
Status: WRTN
Last Updated: 09:43:09 09/11/2014
FPL Page: 1 of 6
Need Date & Time: 09/11/14 07:00
At Station: LINTON Station No: 137
Purpose of Order
WR#4442448 ENERGIZE LOOPS 18565-9 TO 18,18566-7 TO 12,18567-5 TO 14
PRE -SWITCHING CHECKLIST
❑ Communicate:
o Communicate with Dispatchers
o Communicate with Power Plant Control Room if at Plant site
o Perform job briefing with any personnel in the substation
o Identify roles if multiple switchmen
❑ Do I understand the Purpose of the order? If not, then STOP and obtain the necessary information
❑ If switching in a Substation, does the switching order match the operating diagram?
❑ Within the Substation Control House:
o Check the alarm panels and phone board for abnormal conditions & other switching/clearance
paperwork
o Address any issues before proceeding
❑ Fill out individual tags for each Clearance/Permit number listed on the switching order
❑ Put on all required PPE. Verify condition of hot sticks and other switching tools.
❑ Perform a walkthrongh of the area to:
o Check for abnormal conditions
o Identify equipment being switched and changes to current path
o Identify potential hazards: condition of equipment, walking/working surfaces, insects, etc...
LIST:
❑ Utilize Hunan Performance tools for each switching step
Form 970 Rev. 4/7/14
FPL
Swilerson:
,At Station: LINTON
Verify with Dispatcher:
Switching Order: 40727-A-14
Status: WRTN
Last Updated: 09:43:09 09/11/2014
Page: 2 of 6
Need Date & Time: 09/11/14 07:00
Station Name & Number
Switching Order Number & Number of Steps
_ Last update date & time
Names of all Permit Holders (as applicable)
Permit Numbers:
On Circuit Or Equipment
18565-9,18565-18,18566-7,18566-12,18567-5,18567-14
Station No: 137
Given By:
Dispatcher Date & Time
IMPORTANT - READ THESE INSTRUCTIONS FIRST
❑ A. As each step is executed VISUALLY VERIFY proper position of switchblades,
semaphores and motor operators.
❑ B. Execute in the EXACT SEQUENCE GIVEN.
❑ C. If ANY DISCREPANCY is noted, STOP IMMEDIATELY AND REPORT TO THE
DISPATCHER.
Time CPT &— Verified or
_Step Step Description Device Visually Verified Completed By
1
Complete Pre -Switching Checldist
2
IRead Instructions ABC at Top
More Steps
Form 970 Rev. 4/7/14
r.
FPL
SwPerson:
At Station: LINTON
Switching Order: 40727-A-14
Status: WRTN
Last Updated: 09:43:09 09/11/2014
Page: 3 of 6
Need Date & Time: 09/11/14 07:00
Station No: 137
More Steps
Form 970 Rev. 4/7/14
Time CPT & Verified or
Step Step Description Device Visually Verified Completed By
3
Check CLOSED 18565-12
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
4
Check CLOSED
18566-8
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
5
ICheckCLOSED
18567-6
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
6
Check OPEN
18565-13
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
7
ICherkOPEN
18566-9
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
8
Check OPEN
18567-7
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
9
ICLOSE
18565-9
T-6 R/O 12 DRIFTWOOD RD ON TLN: 6-8105-5492-0-0
PELICAN LN
10
Verify to Be Energized ri
18565-12
11
ICLOSE
18566-7
T-7/8 R/O 1008 N OCEAN BLVD TLN: 6-8105-6094-0-7
12
Verify to Be Energized 18566-8
13
CLOSE
18567-5
T-9 A/F 925 N OCEAN BLVD TLN: 6-8105-6893-0-3
14
Verify to Be Energized
18567-6
More Steps
Form 970 Rev. 4/7/14
Switching Order: 40727-A-14
Status: WRTN
Last Updated: 09:43:09 09/11/2014
r " L Page: 4 of 6
SwPerson: Need Date & Time: 09/11/14 07:00
At Station: LINTON Station No: 137
More Steps
Form 970 Rev. 4/7/14
Time CPT & Verified or
Step Step Description Device Visually Verified Completed By
15
ICheckCLOSED
18567-8
T-11 1111 N OCEAN BLVD TLN: 6-8105-6996-0-1
16
Check OPEN
18567-9
T-11 1111 N OCEAN BLVD TLN: 6-8105-6996-0-1
17
Check CLOSED
18567-10
T-12 AN 1111 N OCEAN BLVD TLN: 6-8105-6898-0-0
18
Check OPEN
18567-11
T-12 A/F 1111 N OCEAN BLVD TLN: 6-8105-6898-0-0
19
Check CLOSED
18565-14
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
20
Check CLOSED
18566-10
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
21
Check CLOSED
18567-12
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
22
Check OPEN
18565-15
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
23
Check OPEN
18566-11
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
24
Check OPEN
18567-13
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
25
ICLOSE
18567-7
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
26
Verify to Be Energized rr
18567-8
More Steps
Form 970 Rev. 4/7/14
FILL
SwPerson:
At Station: LINTON
Switching Order: 40727-A-14
Status: WRTN
Last Updated: 09:43:09 09/11/2014
Page: 5 of 6
Need Date & Time: 09/11/14 07:00
Station No: 137
More Steps
Form 970 Rev. 4/7/14
Time CPT & Verified or
Step Step Description Device Visually Verified Completed By
27
ICLOSE
18567-9
T-11 1111 N OCEAN BLVD TLN: 6-8105-6996-0-1
28
Verify to Be Energized
18567-10
29
ICLOSE
18567-11
T-12 A/F 1111 N OCEAN BLVD TLN: 6-8105-6898-0-0
30 Verify to Be Energized r
18567-12
31 ICLOSE
18566-9
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
32 lVerify to Be Energized @
18566-10
33 ICLOSE
18565-13
T-10 925 N OCEAN BLV TLN: 6-8105-7395-0-5
34 Verify to Be Energized r
18565-14
35 Check CLOSED
18565-16
T-14 1221 N OCEAN BLVD TLN: 6-8106-7106-0-8
36
ICheck OPEN
18565-17
T-14 1221 N OCEAN BLVD TLN: 6-8106-7106-0-8
37
CLOSE
18565-15
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
38
Verify to Be Energized r
18565-16
More Steps
Form 970 Rev. 4/7/14
Switching Order: 40727-A-14
Status: VMTN
Last Updated: 09:43:09 09/11/2014
FPL Page: 6 of 6
Swperson: Need Date & Time: 09/11/14 07:00
At Station: LfNTON Station No:137
Time CPT & Verified or 1
Step Step Description Device Visually Verified Completed By
39
CLOSE
18565-17
T-14 1221 N OCEAN BLVD TLN: 6-8106-7106-0-8
40
ICLOSE
18566-11
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
41
ICLOSF
18567-13
_
T-13 1711 N OCEAN BLVD TLN: 6-8106-7406-0-4
42
Hot Phase
@ 18565-18, 18566-
12,18567-14
43
CLOSE
18565-18
SW/C/O PRIVATE RD OCEAN BLVD TLN: 6-8106-7005-3-0
44
ICLOSE
18566-12
SW/C/O PRIVATE RD OCEAN BLVD TLN: 6-8106-7005-3-0
45
ICLOSE,
18567-14
SW/C/O PRIVATE RD OCEAN BLVD TLN: 6-8106-7005-3-0
46
JOPFN
18565-9
T-6 R/O 12 DRIFTWOOD RD ON TLN: 6-8105-5492-0-0
PELICAN LN
47
JOPEN
18566-7
T-7/8 ILO 1008 N OCEAN BLVD TLN: 6-8105-6094-0-7
48
OPEN
18567-3
T-7/8 R/O 1008 N OCEAN BLVD TLN: 6-8105-6094-0-7
49
Update DMS & Diagrams
Executed By:
Switchman Date & Time
Reported to Division
Load Dispatcher:
Load Dispatcher Date & Time
Reported Executed to:
Dispatcher
Date & Time
No More Steps
Form 970 Rev. 4/7/14