HomeMy Public PortalAboutOrdinance No. 1261-14 01-21-2014ORDINANCE NO. 1261-14
AN ORDINANCE OF THE CITY OF RICHLAND HILLS, TEXAS
AMENDING VARIOUS PROVISIONS OF CHAPTER 14, "BUILDINGS
AND BUILDING REGULATIONS", TO ADOPT THE 2012 EDITIONS OF
THE INTERNATIONAL BUILDING CODE, INTERNATIONAL FUEL
GAS CODE, INTERNATIONAL ENERGY CONSERVATION CODE,
INTERNATIONAL MECHANICAL CODE, INTERNATIONAL
RESIDENTIAL CODE, INTERNATIONAL PLUMBING CODE,
INTERNATIONAL EXISTING BUILDING CODE, INTERNATIONAL
PROPERTY MAINTENANCE CODE, AND THE 2011 EDITION OF THE
NATIONAL ELECTRIC CODE; PROVIDING FOR THE
MODIFICATION OF THE CODES TO INCORPORATE LOCAL
AMENDMENTS; PROVIDING FOR RECORDING OF THE CODES AS
PUBLIC RECORDS; PROVIDING THAT THIS ORDINANCE SHALL BE
CUMULATIVE OF ALL ORDINANCES; PROVIDING A
SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY FOR
VIOLATIONS; PROVIDING A SAVINGS CLAUSE; PROVIDING FOR
PUBLICATION IN THE OFFICIAL NEWSPAPER; AND PROVIDING AN
EFFECTIVE DATE.
WHEREAS, the City of Richland Hills, Texas is a home rule city acting under its charter
adopted by the electorate pursuant to Article XI, Section 5 of the Texas Constitution and Chapter
9 of the Local Government Code; and
WHEREAS, the City Council has previously adopted the 2003 Editions of the
International Fuel Gas Code, International Energy Conservation Code, International Mechanical
Code, International Residential Code, and International Plumbing Code, the 2006 Editions of the
International Building Code, and the 2008 Edition of the National Electric Code; and
WHEREAS, the City Council desires to update to and adopt the 2012 Editions of the
International Building Code, International Fuel Gas Code, International Energy Conservation
Code, International Mechanical Code, International Residential Code, International Plumbing
Code, International Existing Building Code, International Property Maintenance Code, and the
2011 Edition of the National Electric Code; and
WHEREAS, the City Council of the City of Richland Hills, Texas, desires to provide a
mechanism by which local modifications reflecting the unique needs of the City of Richland
Hills may be made when deemed appropriate; and
WHEREAS, the North Central Texas Council of Governments and City Staff have
recommended adoption of certain amendments to the Codes to reflect locally accepted practice;
and
C:\Users\lcantu\AppData\Local\Microsofr\Windows\Temporary Internet Files\Content.0utlook\SWOFX101 \Code Adoption 2012 (2).docPage I
WHEREAS, the City Council of the City of Richland Hills, Texas, has determined that
the adoption of these Codes as amended herein is in the public interest and therefore deems it
advisable to enact this ordinance.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE
CITY OF RICHLAND HILLS, TEXAS:
SECTION 1.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-31 and 14-32 of Article II "Building Code" of Chapter 14 to read as follows:
"Sec. 14-31. Adopted.
The 2012 Edition of the International Building Code is hereby adopted as the official
electrical code of the City of Richland Hills, Texas. This building code is fully incorporated by
reference as though copied into this ordinance in its entirety. The material contained in the
International Building Code, and any local amendments thereto, shall not be included in any
formal municipal codification of ordinances but shall be maintained as a public record in the
office of the City Secretary and will be available for public inspection and copying during
regular business hours.
Sec. 14-32. Amendments.
The 2012 Edition of the International Building Code, as adopted herein, is hereby
amended as shown on Exhibit AA@ attached hereto."
SECTION 2.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-441 and 14-442 of Article XII "Fuel Gas Code" of Chapter 14 to read as follows:
"Sec. 14-441. Adopted.
The 2012 Edition of the Fuel Gas Code is hereby adopted as the official fuel gas code of
the City of Richland Hills, Texas. This fuel gas code is fully incorporated by reference as though
copied into this ordinance in its entirety. The material contained in the International Fuel Gas
Code, and any local amendments thereto, shall not be included in any formal municipal
codification of ordinances but shall be maintained as a public record in the office of the City
Secretary and will be available for public inspection and copying during regular business hours.
Sec. 14-442. Amendments.
The 2012 Edition of the International Fuel Gas Code, as adopted herein, is hereby
amended as shown on Exhibit AB @ attached hereto."
C:\UsersUcantu\AppData\Local\Microsofr\Windows\Temporary Internet Files\Content.0utlook\SWOFX101\Code Adoption 2012 (2).docPage 2
SECTION 3.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-420 and 14-421 of Article XI "Energy Conservation Code" of Chapter 14 to read as follows:
"Sec. 14-420. Adopted.
The 2012 Edition of the International Energy Conservation Code is hereby adopted as the
official energy conservation code of the City of Richland Hills, Texas. This energy conservation
code is fully incorporated by reference as though copied into this ordinance in its entirety. The
material contained in the International Energy Conservation Code, and any local amendments
thereto, shall not be included in any formal municipal codification of ordinances but shall be
maintained as a public record in the office of the City Secretary and will be available for public
inspection and copying during regular business hours.
Sec. 14-421. Amendments.
The 2009 Edition of the International Energy Conservation Code, as adopted herein, is
hereby amended as shown on Exhibit AC @ attached hereto."
SECTION 4.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-276 and 14-277 of Article VII "Mechanical Code" of Chapter 14 to read as follows:
"Sec. 14-276. Adopted.
The 2012 Edition of the International Mechanical Code is hereby adopted as the official
mechanical code of the City of Richland Hills, Texas. This mechanical code is fully incorporated
by reference as though copied into this ordinance in its entirety. The material contained in the
International Mechanical Code, and any local amendments thereto, shall not be included in any
formal municipal codification of ordinances but shall be maintained as a public record in the
office of the City Secretary and will be available for public inspection and copying during
regular business hours.
Sec. 14-277. Amendments.
The 2012 Edition of the International Mechanical Code, as adopted herein, is hereby
amended as shown on Exhibit AD @ attached hereto."
SECTION 5.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-400 and 14-401 of Article X "Residential Code" of Chapter 14 to read as follows:
C:\Users\lcantuWppData\Local\Microsoft\Windows\Temporary Internet Files\Content.0utlook\SWOFX101\Code Adoption 2012 (2).docPage 3
"Sec. 14-400. Adopted.
The 2012 Edition of the International Residential Code is hereby adopted as the official
residential code of the City of Richland Hills, Texas. This residential code is fully incorporated
by reference as though copied into this ordinance in its entirety. The material contained in the
International Residential Code, and any local amendments thereto, shall not be included in any
formal municipal codification of ordinances but shall be maintained as a public record in the
office of the City Secretary and will be available for public inspection and copying during
regular business hours.
Sec.14-401. Amendments.
The 2012 Edition of the International Residential Code, as adopted herein, is hereby
amended as shown on Exhibit AE @ attached hereto."
SECTION 6.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-146 and 14-147 of Article IV "Plumbing Code" of Chapter 14 to read as follows:
"Sec. 14-146. Adopted.
The 2012 Edition of the International Plumbing Code is hereby adopted as the official
plumbing code of the City of Richland Hills, Texas. This plumbing code is fully incorporated by
reference as though copied into this ordinance in its entirety. The material contained in the
International Plumbing Code, and any local amendments thereto, shall not be included in any
formal municipal codification of ordinances but shall be maintained as a public record in the
office of the City Secretary and will be available for public inspection and copying during
regular business hours.
Sec. 14-147. Amendments.
The 2012 Edition of the International Plumbing Code, as adopted herein, is hereby
amended as shown on Exhibit AF@ attached hereto."
SECTION 7.
The Code of Ordinances, City of Richland Hills, is hereby revised by adding sections 14-
531 and 14-532 to a new Article XVI "Existing Building Code" of Chapter 14 to read as follows:
Sec. 14-531. Adopted.
The 2012 Edition of the International Existing Building Code is hereby adopted as the
official existing building code of the City of Richland Hills, Texas. This existing building code is
fully incorporated by reference as though copied into this ordinance in its entirety. The material
contained in the International Existing Building Code shall not be included in any formal
C:\Users\lcantu\AppData\Local\Microsoft\Windows\Temporary Internet Files\Content.0utlook\SWOFX101\Code Adoption 2012 (2).docPage 4
municipal codification of ordinances but shall be maintained as a public record in the office of
the City Secretary and will be available for public inspection and copying during regular
business hours.
Sec. 14-532. Amendments.
The 2012 Edition of the International Existing Building Code, as adopted herein, is
hereby amended as shown on Exhibit AG@ attached hereto."
SECTION 8.
The Code of Ordinances, City of Richland Hills, is hereby revised by amending sections
14-461 and 14-462 of Article XIII "Property Maintenance Code" of Chapter 14 to read as
follows:
"Sec.14-461. Adopted.
The 2012 Edition of the International Property Maintenance Code is hereby adopted as
the official property maintenance code of the City of Richland Hills, Texas. This property
maintenance code is fully incorporated by reference as though copied into this ordinance in its
entirety. The material contained in the International Property Maintenance Code, and any local
amendments thereto, shall not be included in any formal municipal codification of ordinances but
shall be maintained as a public record in the office of the City Secretary and will be available for
public inspection and copying during regular business hours.
Sec. 14-462. Amendments.
The 2012 Edition of the International Property Maintenance Code, as adopted herein, is
hereby amended as shown on Exhibit AH@ attached hereto."
SECTION 9.
The City of Richland Hills may from time to time determine that additional local
modifications to the code adopted herein are necessary and appropriate to meet the unique needs
of the City of Richland Hills. To effectuate modifications, the city council may enact individual
ordinances amending this ordinance fully setting forth the changes to be made. Such subsequent
amendments shall be consolidated as an exhibit to this ordinance, and shall be maintained as a
public record in the office of the city secretary, available for public inspection and copying
during regular business hours.
SECTION 10.
This Ordinance shall be cumulative of all provisions of ordinances of the City of
Richland Hills, except where the provisions of this ordinance are in direct conflict with the
provisions of such ordinances, in which event the conflicting provisions of such ordinances are
hereby repealed.
C:\Users\lcantuWppData\Local\Microsoft\Windows\Temporary Internet Files\Content.0utlook\SWOFX101\Code Adoption 2012 (2).docPage 5
SECTION 11.
It is hereby declared to be the intention of the City Council that the phrases, clauses,
sentences, paragraphs and sections of this Ordinance are severable, and if any phrase, clause,
sentence, paragraph or section of this Ordinance shall be declared unconstitutional by the valid
judgment or decree of any court of competent jurisdiction, such unconstitutionality shall not
affect any of the remaining, phrase, clauses, sentences, paragraphs or sections of this Ordinance
since the same would have been enacted by the City Council without incorporation in this
Ordinance of any such unconstitutional phrase, clause, sentence, paragraph or section.
SECTION 12.
Any person, firm or corporation who violates, disobeys, omits, neglects or refuses to
comply with or who resists the enforcement of any of the provisions of this Ordinance shall be
fined no more than Two Thousand Dollars ($2,000.00) for all violations involving zoning, fire
safety or public health and sanitation, including dumping or refuse, and shall be fined not more
than Five Hundred Dollars ($500.00) for all other violations of this Ordinance. Each day that a
violation is permitted to exist shall constitute a separate offense.
SECTION 13.
All rights and remedies of the City of Richland Hills, Texas, are expressly saved as to any
and all violations of the provisions of any ordinances of the City of Richland Hills which have
accrued at the time of the effective date of this Ordinance; and, as to such accrued violations and
all pending litigation, both civil and criminal, whether pending in court or not, under such
ordinances same shall not be affected by this Ordinance but may be prosecuted until final
disposition by the courts.
SECTION 14.
The City Secretary of the City of Richland Hills is hereby authorized to publish this
ordinance in book or pamphlet form for general distribution among the public, and the operative
provisions of this ordinance as so published shall be admissible in evidence in all courts without
further proof than the production thereof.
SECTION 15.
The City Secretary of the City of Richland Hills is directed to publish the caption and
penalty clause of this Ordinance in the official newspaper of the City of Richland Hills, Texas, as
required by Section 52.011 of the Texas Local Government Code.
SECTION 16.
This Ordinance shall be in full force and effect form and after its passage and publication
as provided by law, and it is so ordained.
C:\Users\lcantu\AppData\Local\Microsoft\Windows\Temporary Internet Files\Content.0utlook\SWOFX101\Code Adoption 2012 (2).docPage 6
PASSED AND APPROVED~DAY OF , 2014.
THE HONORABLE AGAN, MAYOR
ATTEST:
INDA CANTU, CITY SECRETARY ~ ~-
_ _,,,,
./-,
EFFECTIVE DATE: ~` ~ ~
APPROVED AS TO FORM AND LEGALITY: //''/~~~~~"" ~ ~ ~ ~ ~ ~ ~ ~ "`~~~~\\\\\\
STEVEN A. WOOD, CITYATTORNEY
W:\Itichland Hills\Ordinance\2012 Int. CodeslCode Adoption.2012.doc Page 7
Recommended Amendments to the
2012 International Building Code
North Central Texas Council of Governments Region
The following sections, paragraphs, and sentences of the 2012 International Building Code are hereby
amended as follows: Standard type is text from the IBC. Underlined tvpe is text inserted. ~ ~^~^' +~~^~~^"
+,,•,~ ;~ '~~l°t°d text fr~m~~. A double asterisk ('`*) at the beginning of a section identifies an amendment
carried over from the 2009 edition of the code and a triple asterisk (***) identifies a new or revised
amendment with the 2012 code.
Explanation of Options A and B:
Please note that as there is a wide range in fire fighting philosophies /capabilities of cities across the
region, OPTION "A" and OPTION "B" are provided in the Fire and Building Code amendments.
Jurisdictions should choose one or the other based on their fire fighting philosophies /capabilities
when adopting code amendments.
Note: Historically NCTCOG has limited chapter 1 amendments in order to allow each city to insert their
local policies and procedures. We now have suggested certain items to be brought to the attention of
cities considering adoption of the code that may be of concern to several jurisdictions. It is still intended
to be discretiona to each cit to determine which chapter 1 amendments to include.
,.,- ~ ..
**Section 101.4; change to read as follows:
101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.6 and referenced
elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this
code to the prescribed extent of each such reference. Whenever amendments have been adopted to the
referenced codes and standards each reference to said code and standard shall be considered to
reference the amendments as well. Any reference to NFPA 70 or the Electrical Code shall mean the
Electrical Code as adopted.
(Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced
codes. The former ICC Electrical Code is now Appendix K of this code but no longer called by that name.)
*"Section 101.4.7; add the following:
101.4.7 Electrical. The provisions of the Electrical Code shall apply to the installation of electrical
systems including alterations repairs replacement equipment appliances fixtures fittings and
appurtenances thereto.
(Reason: This was dropped when ICC quit publishing the ICC Electrical Code, but the Electrical Code still
should be referenced regardless of how it is adopted.)
** Section 103 and 103.1 amend to insert the Department Name
SECTION 103
IIQDADTIIACAIT ~1C Q1111 ni~ii- enc~TV [INSERT OFFICIAL BUILDING DEPARTMENT
NAME OF JURISDICTIONI
103.1 Creation of enforcement agency. The [INSERT OFFICIAL
BUILDING DEPARTMENT NAME OF JURISDICTION] is hereby created and the official in charge thereof
shall be known as the building official.
Reminder to be sure ordinance reads the same as designated by the
North Central Texas Council of Governments 1 January 21, 20142012 IBC Amendments
Building:
~} ,
nnoc n~~ .~.. Dior 7 fo~+ /1 Q70 mm\ hirrh
1. (Unchanged)
4. 2. (Unchanged)
3. (Unchanged)
6- 4. (Unchanged)
5. (Unchanged)
8- 6. (Unchanged)
7. (Unchanged)
8. (Unchanged)
~? 9. (Unchanged)
10. (Unchanged)
(Reason: Items deleted are for one- and two-family dwellings regulated by the International Residential
Code. Accessory structures, fences and shade cloth structures would require a permit for commercial
properties to ensure compliance with local ordinance, egress, accessibility, flame spread of fabric,
wind/snow design load, etc.).
**Section 109; add Section 109.7 to read as follows:
109.7 Re-inspection Fee. A fee as established by city council resolution may be charged when
1. The inspection called for is not ready when the inspector arrives
2. No building address or permit card is clearly posted;
3. City approved plans are not on the iob site available to the inspector
4. The building is locked or work otherwise not available for inspection when called
5. The job site is red-tagged twice for the same item;
6. The original red tag has been removed from the iob site.
7. Failure to maintain erosion control, trash control or tree protection.
Any re-inspection fees assessed shall be paid before any more inspections are made on that iob site
(Reason: This fee is not a fine or penalty but is designed to compensate for time and trips when
inspections are called for when not ready.)
**Section 109; add Section 109.8, 109.8.1, 109.8.2 and 109.9 to read as follows:
North Central Texas Council of Governments 2 January 21, 20142012 IBC Amendments
109.8 Work without a permit.
109.8.1 Investigation. Whenever work for which a permit is required by this code has been
commenced without first obtaining a permit, a special investigation shall be made before a permit
may be issued for such work.
109.8.2 Fee. An investigation fee, in addition to the permit fee, shall be collected whether or not a
permit is subsequently issued. The investigation fee shall be equal to the amount of the permit fee
required by this code or the city fee schedule as applicable The payment of such investigation fee
shall not exempt the applicant from compliance with all other provisions of either this code or the
technical codes nor from penalty prescribed by law.
109.9 Unauthorized cover up fee Any work concealed without first obtaining the required inspection in
violation of Section 110 shall be assessed a fee as established by the city fee schedule.
(Reason: This fee is not a fine or penalty but is designed to compensate for time and to remove incentive
to attempt to evade permits and code compliance. Text taken from former Uniform Administrative Code.)
**Section 110.3.5; jurisdiction has the option to delete depending on local inspection policies.
(Reason: Lath or gypsum board inspections are not normally performed in this area.)
**Section 202; amend definition of Ambulatory Care Facility as follows:
AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical,
psychiatric, nursing or similar care on a less than 24-hour basis to individuals who are rendered incapable
of self-preservation by the services provided. This group may include but not be limited to the following:
- Dialysis centers
- Sedation dentistry
- Surgery centers
- Colonic centers
- Psychiatric centers
(Reason: To clarify the range of uses included in the definition. (Explanatory note related to Ambulatory
Care Facilities: This group of uses as defined in Chapter 2 includes a medical or dental office where
persons are put under for dental surgery or other services. Section 903.2.2 will now require such uses to
be sprinklered if on other than the floor of exit discharge or if four or more persons are put under on the
level of exit discharge. Recommend (1.) jurisdictions document any pre-existing non-conforming
conditions prior to issuing a new C of O for a change of tenant and, (2.) On any medical or dental office
specify on C of O the maximum number of persons permitted to be put under general anesthesia.
It is recommended that before a Certificate of Occupancy is issued, a letter of intended use from the
business owner shall be included and a C of O documenting the maximum number of care recipients
incapable of self preservation allowed.)
*"*Section 202; add definition of Assisting Living Facilities to read as follows.
ASSISTED LIVING FACILITIES. A building or part thereof housing persons, on a 24-hour basis, who
because of age, mental disability or other reasons, live in a supervised residential environment which
provides personal care services. The occupants are capable of responding to an emergency situation
without physical assistance from staff.
(Reason: The code references Assisted Livin facilities and definition was deleted)
~. ,
**Section 202; change definition of "Atrium" as follows:
ATRIUM. An opening connecting tws three or more stories... {Balance remains unchanged}
(Reason: Accepted practice in the region based on legacy codes. Section 1009 permits unenc/osed two
story stairways under certain circumstances.)
North Central Texas Council of Governments 3 January 21, 20142012 IBC Amendments
Option A
**Section 202; {No amendment necessary}
**Section 202; amend definition to read as follows:
Option B
HIGH-RISE BUILDING. A building with an occupied floor located more than ~5 55 feet r" Qom;,;
(16 764 mm) above the lowest level of fire department vehicle access.
(Reason: To define high-rise, as it influences sprinkler requirement thresholds based on the fire fighting
capabilities of a jurisdiction. This correction needed for Option B and C cities only as a basic definition of
High Rise is now provided.)
***Section 303.1.3; add a sentence to read as follows:
303.1.3 Associated with Group E occupancies. A room or space used for assembly purposes that is
associated with a Group E occupancy is not considered a separate occupancy- except when applying the
assembly requirements of Chapter 10 and 11.
(Reason: To clarify that egress and accessibility requirements are applicable for assembly areas, i. e.
cafeteria, auditoriums, etc.)
**Section 304.1; add the following to the list of occupancies:
Fire stations
Police stations with detention facilities for 5 or less
Consistent with regional practice dating back to the legacy codes.
**Section 307.1; add the following sentence to Exception 4:
4. Cleaning establishments... {text unchanged} ...with Section 707 or 1-hour horizontal assemblies
constructed in accordance with Section 711 or both. See also IFC Chapter 12, Dry Cleaning Plant
provisions.
(Reason: To call attention to detailed requirements in the Fire Code.)
""Section 403.1, Exception 3; change to read as follows:
3. Open air portions of buildings i~+ld+ngs with a Group A-5 occupancy in accordance with Section
303.6.
(Reason: To clarify enclosed portions are not exempt.)
**Section 403.3, Exception; delete item 2.
To provide adequate fire protection to enclosed areas.
**Section 404.5; delete Exception.
Consistent with amended atrium
**Section 406.3.2; add item 3 to read as follows:
North Central Texas Council of Governments 4 January 21, 20142012 IBC Amendments
3. A separation is not reauired between a Group R-2 and U carport provided that the carport is
entirely open on all sides and that the distance between the two is at least 10 feet (3048 mm)
(Reason: Simplifies the fire separation distance and eliminates the need to obtain opening information on
existing buildings when adding carports in existing apartment complexes. Consistent with legacy codes in
effect in re ion for ears and no record of roblems with car fires s readin to apartments as a result.)
*"Section 406.8; add a second paragraph to read as follows:
This occupancy shall also include garaaes involved in minor repair modification and servicina of motor
vehicles for items such as tube changes inspections windshield repair or replacement shocks minor
part replacement and other such minor repairs.
(Reason: To further clarify types of service work allowed in a repair garage, as well as to correspond with
definition in the IFC.)
**Section 506.2.2; add sentence to read as follows:
506.2.2 Open Space Limits. Such open space shall be either on the same lot or dedicated for public use
and shall be accessed from a street or approved fire lane. In order to be considered as accessible if not
in direct contact with a street or fire lane a minimum 10-foot wide pathway meeting fire department
access from the street or approved fire lane shall be provided.
(Reason: To define what is considered accessible. Consistent with re Tonal amendment to /FC 504.1.)
**Section 712.1.8, change item 5 to read as follows:
5. Is not open to a corridor in Group I and # H occupancies.
(Reason: To be consistent with re ionall acce ted ractices.)
**Section 713.14.1 Elevator Lobby. Exceptions: 4.3 change to read as follows:
Option A
***Section 713.14.1; Exception 4.3 {No amendment necessary}
Option B
*"*Section 713.14.1; Exception 4.3 Elevators serving floor levels over 7~ 55 feet "~ R~
764 mm above the lowest level of fire department vehicle access in high rise buildings.
(Reason: This correction needed for Option B and C cities only as a basic definition of High Rise is now
provided.)
**Section 903.1.1; change to read as follows:
[F] 903.1.1 Alternative protection. Alternative automatic fire-extinguishing systems complying with
Section 904 shall be permitted in lie~+-ef addition to automatic sprinkler protection where recognized by
the applicable standard arm, or as approved by the fire code official.
(Reason: Such alternative systems do not provide the reliability of automatic sprinkler protection in
general. An applicant could pursue an Alternate Method request to help mitigate the reliability issues with
these alternative systems with the fire code official if so desired, or there may be circumstances in which
the fire code official is acceptable to allowing an alternate system in lieu of sprinklers, such as kitchen
hoods or paint booths. This also meets with local practices in the region.)
North Central Texas Council of Governments 5 January 21, 20142012 IBC Amendments
**Section 903.2; add the following:
[F] 903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall
be provided in the locations described in Sections 903.2.1 through 903.2.12. Automatic Sprinklers shall
not be installed in elevator machine rooms, elevator machine spaces and elevator hoistways other than
pits where such sprinklers would not necessitate shunt trip requirements under any circumstances
Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry
doors to the elevator machine room indicating "ELEVATOR MACHINERY - NO STORAGE ALLOWED "
(Reason: Firefighter and public safety. This amendment eliminates the shunt trip requirement of the
International Building Code Section 3006.5 for the purpose of elevator passenger and firefighter safety.
This amendment is contingent on the Building Code amendment eliminating the Exceptions to Section
3006.4, such that passive fire barriers for these areas are maintained. This also meets with local practices
in the region.)
"*Section 903.2; delete the exception. r
(Reason: The exception deletion is due to the fact that such telecom areas pose an undue fire risk to the
structural integrity of the building. This also meets with local practices in the region.)
Options A and B
Section 903.2.1.2; No
**Section 903.2.9; add Section 903.2.9.3 to read as follows:
[F] 903.2.9.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout
all self-service storage facilities.
Exception: One-story self-service storage facilities that have no interior corridors with cone-hour fire
barrier separation wall installed between every storage compartment.
(Reason: Fire departments are unable to inspect these commercial occupancies and are unaware of the
contents being stored. This also meets with local practices in the region.)
Option A
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, and 903.2.11.8, as follows:
[F] 903.2.11.3 Buildings 55 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International Building Code, that is located 55 feet (16 764
mm) or more above the lowest level of fire department vehicle access.
Exceptions:
-Open parking structures in compliance with Section 406.5 of the Building Code.
903.2.11.7 High-Piled Combustible Storage For any building with a clear height exceeding 12 feet
L4572 mm), see IFC Chapter 32 to determine if those provisions appl rL
North Central Texas Council of Governments 6 January 21, 20142012 IBC Amendments
903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire-extinguishing system.
Option B
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows:
903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International Building Code, that is located as 35 feet 0764
10 668mm) or more above the lowest level of fire department vehicle access.
Exceptions:
Open parking structures in compliance with Section 406.5 of the International Building Code.
903.2.11.7 High-Piled Combustible Storage For any building with a clear height exceeding 12 feet
(4572 mm) see IFC Chapter 32 to determine if those provisions appl rL
903.2.11.8 Spray Booths and Rooms New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire-extinguishing system.
903.2.11.9 Buildings Over 6,000 sq.ft. An automatic sprinkler system shall be installed throughout
all buildings with a building area over 6,000 sq.ft. For the purpose of this provision, fire walls shall
not define separate buildings.
Exception: Open parking garages in compliance with Section 406.5 of the International Building
Code.
(Reason: Reflects regional practices.)
***Section 903.3.1.1.1; change to read as follows:
[F] 903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic sprinklers shall not
be required in the following rooms or areas where such ...{text unchanged}... because it is damp, of fire-
resistance-rated construction or contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire
hazard.
2. Any room or space where sprinklers are considered undesirable because of the nature of the
contents, when approved by the code official.
3. Generator and transformer rooms, under the direct control of a public utility, separated from the
remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having afire-
resistance rating of not less than 2 hours.
5. F~'ti °°^~~^° ^^^°^~ Elevator machine rooms, machinery spaces, and hoistways,other than pits
where such sprinklers would not necessitate shunt trip requirements under any circumstances.
6. {Delete.}
North Central Texas Council of Governments 7 January 21, 20142012 IBC Amendments
(Reason: Gives more direction to code official. Exception 4 deleted to provide protection where fire risks
are poorly addressed. Amendment 903.2 addresses Exception 5 above relative to the elimination of
sprinkler protection in these areas to avoid the shunt trip requirement.
***Section 903.3.1.2.2; add the following:
[F]Section 903.3.1.2.2 Attics, Open Breezeways, and Attached Garages. Sprinkler protection is
required in attic spaces of such buildings two or more stories in height, open breezeways, and attached
garages.
(Reason: Open breezeways already require sprinkler protection in Section 1026.6, Exception 4. Attic
protection is required in accordance with existing regional practice and issues with fire exposure via soffit
vents, as well as firefighter safety. Attached garages already require sprinkler via NFPA 13R - re-
emphasis.)
**Section 903.3.1.3; add the following:
[F] 903.3.1.3 NFPA 13D sprinkler systems. Automatic sprinkler systems installed in one- and two-family
dwellings, Group R-3 and R-4 congregate living facilities and townhouses shall be permitted to be
installed throughout in accordance with NFPA 13D or in accordance with state law.
(Reason: To allow the use of the Plumbing section of the IRC and recognize current state stipulations in
this regard.)
**Section 903.3.5 Water Supplies; add a second paragraph to read as follows:
[Fl Water supply as required for such systems shall be provided in conformance with the supply
requirements of the respective standards; however, every fire protection system shall be designed with a
10 psi safety factor. Reference Section IFC 507.4 for additional design requirements
(Reason: To define uniform safety factor)
**Section 903.4 Sprinkler system supervision and alarms; add a second paragraph after the
exceptions to read as follows:
IFl Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the
sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds All
control valves in the sprinkler and standpipe systems except for fire department hose connection valves
shall be electrically supervised to initiate a supervisory signal at the central station upon tampering
(Reason: To avoid significant water losses. Consistent with amendment to IFC 905.9.)
**Section 903.4.2 Alarms; add second paragraph to read as follows:
[Fl The alarm device required on the exterior of the building shall be a weatherproof horn/strobe
notification appliance with a minimum 75 candela strobe rating installed as close as practicable to the fire
department connection.
(Reason: Fire department connections are not always located at the riser,' this allows the fire department
faster access.)
**Section 905.2 Installation standard; change to read as follows:
jF]_905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and
NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psiq and a maximum
of 40 psig air pressure with ahigh/low alarm.
(Reason: To define manual dry standpipe supervision requirements. Helps ensure the integrity of the
standpipe system via supervision, such that open hose valves will result in a supervisory low air alarm.)
North Central Texas Council of Governments 8 January 21, 20142012 IBC Amendments
***Add Section 905.3.9 and exception to read as follows:
[Fl 905.3.9 Building area. In buildings exceeding 10 000 square feet in area per story Class I automatic
wet or manual wet standpipes shall be provided where any portion of the building's interior area is more
than 200 feet (60960 mm) of travel, vertically and horizontally from the nearest point of fire department
vehicle access.
Exception: Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA
14.
Allows for the rapid deployment of hoselines to the body of the
**Section 905.4, item 5; change to read as follows:
[F] 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent
slope), each standpipe shall be provided with atwo-way a--hose connection she located to
serve the roof or at the highest landing of a stairway with stair access to the roof provided in
accordance with Section 1009.16. An additional hose connection shall be provided at the top of
the most hydraulically remote standpipe for testing purposes.
(Reason: Maintains previously adopted amendment for the following purpose. Reduced the amount of
ressure re uired to facilitate testin ,and provides backu rotection for fire fi hter safet .)
**Section 905.4 Location of Class I standpipe hose connections; add the following item 7:
[F] 7. When required by this Chapter, standpipe connections shall be placed adjacent to all required
exits to the structure and at two hundred feet (200') intervals along major corridors thereafter
(Reason: Allows for the rapid de loyment of hoselines to the body of the fire.)
**Section 905.9 Valve supervision; add a second paragraph after the exceptions to read as
follows:
[F] Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the
sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds Alt
control valves in the sprinkler and standpipe systems except for fire department hose connection valves
shall be electrically supervised to initiate a supervisory signal at the central station upon tampering_
(Reason: To avoid si nificant water losses. Consistent with amendment to IFC 903.4.)
**Add Section 907.1.4 to read as fo/lows:
LFl 907.1.4 Design standards. All alarm systems new or replacement shall be addressable Alarm
systems serving more than 20 smoke detectors shall be analog addressable
Exception: Existing systems need not comply unless the total building remodel or expansion
initiated after the effective date of this code, as adopted exceeds 30% of the building When cumulative
building remodel or expansion exceeds 50% of the building must comply within 18 months of permit
application.
(Reason: Consistent with local practice and emerging technology. Reduces need for panel replacement in
the future.)
**Section 907.2.1; change to read as follows:
[F] 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in
accordance with new Section 907.6 shall be installed in Group A occupancies having an occupant load of
North Central Texas Council of Governments 9 January 21, 20142012 IBC Amendments
300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group
A occupancies not separated from one another in accordance with Section 707.3.9 of the International
Building Code shall be considered as a single occupancy for the purposes of applying this section.
Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm
system as required for the Group E occupancy.
Exception: {unchanged.}
Activation of fire alarm notification appliances shall:
1. Cause illumination of the means of eoress with light of not less than 1foot-candle (11 lux) at the
walking surface level, and
2. Stop anv conflicting or confusing sounds and visual distractions
(Reason: Increases the requirement to be consistent with Group B requirement. Also addresses issue
found in Group A occupancies of reduced lighting levels and other A/V equipment that distracts from fire
alarm notification devices. Also reflects regional practice.)
**Section 907.2.3; change to read as follows:
[F] 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an
emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and
installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When
automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be
connected to the building fire alarm system. An approved smoke detection svstem shall be installed in
Group E day care occupancies. Unless separated by a minimum of 100' open space all buildings
whether portable buildings or the main building will be considered one building for alarm occupant load
consideration and interconnection of alarm systems.
(Reason: To distinguish educational from day care occupancy minimum protection requirements. Further,
to define threshold at which portable buildings are considered a separate building for the purposes of
alarm systems.)
**Section 907.2.3; add exception 1.1 to read as follows:
[F] Exceptions:
1. A manual fire alarm system is not required in Group E educational and day care occupancies
with an occupant load of 30 or less when provided with an approved automatic sprinkler
svstem.
1.1. Residential In-Home day care with not more than 12 children may use interconnected
single station detectors in all habitable rooms. (For care of more than five children 2 1/2
or less years of age, see Section 907.2.6.)
(Reason: Consistent with Texas State laws concerning day care facility requirements.)
(Reason: Hel s to reduce false alarms. Consistent with regional requirements.)
**Add Section 907.6.1.1 to read as follows:
[Fl 907.6.1.1 Wiring Installation. All fire alarm svstems shall be installed in such a manner that a failure
of anv single initiating device or single open in an initiating circuit conductor will not interfere with the
North Central Texas Council of Governments 10 January 21, 20142012 IBC Amendments
normal operation of other such devices All signaling line circuits (SLC) shall be installed in such a way
that a single open will not interfere with the operation of anv addressable devices (Class A) Outgoing and
return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits
and shall have a minimum of four feet separation horizontal and one foot vertical between supply and
return circuit conductors. The initiating device circuit (IDC) from an addressable input (monitor) module
may be wired Class B, provided the distance from the addressable module to the initiating device is ten
feet or less.
(Reason: To provide uniformity in system specifications and guidance to design engineers. Improves
reliability of fire alarm devices and systems.)
**Add Section 907.6.5.3 to read as follows:
[Fl 907.6.5.3 Communication reauirements. All alarm systems new or replacement shall transmit
alarm, supervisory and trouble signals descriptively to the approved central station remote supervisory
station or proprietary supervising station as defined in NFPA 72 with the correct device designation and
location of addressable device identification. Alarms shall not be permitted to be transmitted as a General
Alarm or Zone condition.
To assist responding personnel in locating the emergency event.
**Section 910.1; change Exception 2 to read as follows:
[F] 2. Where areas of buildings are equipped with early suppression fast-response (ESFR)
sprinklers, auteonly manual smoke and heat vents shall +~et-be required within these areas.
Automatic smoke and heat vents are prohibited.
(Reason: Allows the fire department to control the smoke and heat during and after a fire event.)
*** Section 910.2 Where required to read as follows:
[F] {Text unchanged}......Sections 910.2.1 a~through 910.2.2 4
Added numbers 910.2.3 and 910.2.
**Add subsections 910.2.3 with exceptions to read as follows:
[Fl 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows
1. In occupancies classified as Group H-2 or H-3 anv of which are more than 15 000 square feet
(1394 m) in single floor area.
Exception: Buildings of noncombustible construction containing only noncombustible materials
2. In areas of buildings in Group H used for storing Class 2 3 and 4 liquid and solid oxidizers Class
1 and unclassified detonable organic peroxides Class 3 and 4 unstable (reactive) materials or
Class 2 or 3water-reactive materials as reauired for ahigh-hazard commodity classification
Exception: Buildings of noncombustible construction containing only noncombustible materials
(Reason: Provides an acceptable alternative for large storage and manufacturing occupancies, rather
than requiring interior rated exit passageways, as has been allowed for many years.)
**Add subsections 910.2.4 to read as follows:
jFl 910.2.4 Exit access travel distance increase. Buildings and portions thereof used as a Group F-1 or
S-1 occupancy where the maximum exit access travel distance is increased in accordance with Section
1016.2.2.
North Central Texas Council of Governments 11 January 21, 20142012 IBC Amendments
(Reason: Provides an acceptable alternative for large storage and manufacturing occupancies, rather
than requiring interior rated exit passageways, as has been allowed for many years.)
**Table 910.3; Change the title of the first row of the table from "Group F-1 and S-1" to include
"Group H" and to read as follows:
Group H F-1 and S-1
(Reason: Consistency with the amendment 910.2.3 to include Group H.)
**Add Section 912.2.3 to read as follows:
[Fl 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the fire
department connection as the fire hose lays along an unobstructed path.
(Reason: Consistent with regional practices.)
**Section 913.1; add second paragraph and exception to read as follows:
[Fl When located on the ground level at an exterior wall, the fire pump room shall be provided with an
exterior fire department access door that is not less than 3 ft. in width and 6 ft - 8 in in height regardless
of any interior doors that are provided. A key box shall be provided at this door as required by IFC
Section 506.1.
Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior
wall, the corridor leading to the fire pump room access from the exterior of the building shall be
provided with equivalent fire resistance as that reauired for the pump room or as approved by the fire
code official. Access keys shall be provided in the key box as reauired by IFC Section 506.1.
(Reason: This requirement allows fire fighters safer access to the fire pump room. The requirement
allows access without being required to enter the building and locate the fire pump room interior access
door during a fire event. The exception recognizes that this will not always be a feasible design scenario
for some buildings, and as such, provides an acceptable alternative to protect the pathway to the fire
pump room.)
**Section 1004.1.2; delete exception:
1004.1.2 Areas without fixed seating. The number of occupants shall be computed at the rate of one
occupant per unit of area as prescribed in Table 1004.1.2. For areas without fixed seating, the occupant
load shall not be less than that number determined by dividing the floor area under consideration by the
occupant load factor assigned to the function of the space as set forth in Table 1004.1.2. Where an
intended function is not listed in Table 1004.1.2, the building official shall establish a function based on a
listed function that most nearly resembles the intended function.
(Reason: Authority having jurisdiction (AHJ) already has this authority. Technical substantiation is
required to support deviation from table values.)
**Section 1007.1; add the following Exception 4:
Exceptions:
North Central Texas Council of Governments 12 January 21, 20142012 IBC Amendments
{previous exceptions unchanged}
4. Buildings regulated under State Law and built in accordance with State registered plans including
any variances or waivers granted by the State, shall be deemed to be in compliance with the
requirements of Section 1007.
(Reason: To accommodate buildings regulated under Texas State Law and to be consistent with
amendments to Chapter 11.)
*** Section 1007.5; Platform lifts, amend to read as follows:
1007.5 Platform lifts. Platform (wheelchair) lifts ...required accessible route in Section 1109.E 8, Items
1 through 810. Standby power .. {remainder unchanged}
(Reason: Editorial.)
*"*Section 1008.1.9.4; amend exceptions 3 and 4 as follows:
Exceptions:
3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S
occupancy. {Remainder unchanged}
4. Where a pair of doors serves a Group A, B, F, M or S occupancy. {Remainder unchanged}
(Reason: Application to M occupancies reflects regional practice; No. 4 expanded to Group
A due to it being a similar scenario to other uses; No. 4 was regional practice.)
**Section 1008.1.9.9; change to read as follows:
1008.1.9.9 Electromagnetically locked egress doors. Doors in the means of egress in buildings with
an occupancy in Group A, B, E, I-1, I-2, M, R-1 or R-2 and doors to tenant spaces in Group A, B, E, I-1, I-
2 M, R-1 or R-2 shall be permitted to be electromagnetically locked if equipped with listed hardware that
incorporates abuilt-in switch and meet the requirements below: {remaining text unchanged}
(Reason: Re Tonal ractice to ermit such locks due to the resence of trained staff.)
**Section 1015; add new section 1015.7 to read as follows:
1015.7 Electrical Rooms. For electrical rooms, special exiting requirements may apply Reference the
electrical code as adopted.
(Reason: Cross reference necessary for coordination.)
**`Section 1016; add new section 1016.2.2 to read as follows:
1016.2.2 Group F-1 and S-1 increase. The maximum exit access travel distance shall be 400 feet (122
m) in Group F-1 or S-1 occupancies where all of the following are met:
1. The portion of the building classified as Group F-1 or S-1 is limited to one story in height
2. The minimum height from the finished floor to the bottom of the ceiling or roof slab or deck is 24
feet (7315 mm); and
3. The buildina is equipped throughout with an automatic fire sprinkler system in accordance with
Section 903.3.1.1.
(Reason: Past regional practice allowed smoke and heat vents to be utilized to increase travel distance,
which resulted in problems when utilizing ESFR systems. This amendment adopts wording from the
upcoming 2015 IBC, which has been approved by final action via the ICC code development process but
is not yet published.)
North Central Texas Council of Governments 13 January 21, 20142012 IBC Amendments
***Section 1018.1; add exception 6 to read as follows:
{previous text unchanged}
6. In Group B office buildings corridor walls and ceilings within single tenant spaces need not be of
fire-resistive construction when the tenant space corridor is provided with svstem smoke
detectors tied to an approved automatic fire alarm. The actuation of anv detector shall activate
alarms audible in all areas served by the corridor.
(Reason: To reduce redundant requirements in a single tenant situation. Intended to be consistent with
regional amendment to IFC.
**Section 1018.6; amend to read as follows:
1018.6, Corridor Continuity. Ciro oo~,~+.,T,,.o o..+e,~ All corridors shall be continuous from the point of
1 TGiTGOTGiFrIpTYIZQCGQ
entry to an exit, and shall not be interrupted by intervening rooms. {Remainder unchanged}
{Exception unchanpedj
(Reason: Once in corridor, corridor should not be interrupted or discontinuous.)
**Section 1026.6; amend exception 4 to read as follows:
Exceptions: {Exceptions 1 through 3 unchanged}
4. Separation from the +r~teraer open-ended corridors of the building... {remaining text unchanged}
(Reason: To clarify that Section 1022.7, i. e., the 180 degree rule is applicable; and is further reinforced by
new Exception 4.4.)
***Section 1028.1.1.1; delete.
(Reason: Unenforceable.)
***Section 1029.1; amend to read as follows:
1029.1 General. In addition to the means of egress required by this chapter, provisions shall be made
for emergency escape and rescue openings in Group R and I-1 6f6~p-R-2 occupancies
. . {Remainder unchanged}
Exceptions:
{Exceptions 1 through 3 unchanged.}
4. In other than Group R-3 occupancies, buildings equipped throughout with an
approved automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2.
(Reason: Maintains legacy language to ensure egress from residential type occupancies and maintain
exception for residential occupancies where an NFPA 13 or 13R sprinkler system is installed, but not for a
13D system.)
**Section 1101.2; Add exception to read as follows:
Exceptions: Projects registered with the Architectural Barriers Division of the Texas Department of
Licensing and Regulation shall be deemed to be in compliance with the requirements of this Chaoter
(Reason: To accommodate buildings regulated under state law.)
***Section 1203.1; amend to read as follows:
North Central Texas Council of Governments 14 January 21, 20142012 IBC Amendments
***1203.1 General. Buildings shall be provided with natural ventilation in accordance with Section
1203.4, or mechanical ventilation in accordance with the International Mechanical Code.
Where air infiltration rate in a dwelling unit is'°,~+~^ 5 air changes or less per hour when tested
with a blower door at a pressure 0.2 inch w.c. (50 Pa) in accordance with Section 402.4.1.2 of the
International Energy Conservation Code, the dwelling unit shall be ventilated by mechanical means in
accordance with Section 403 of the International Mechanical Code.
(Reason: See IECC change to performance testing. Whole-house ventilation is recogni2ed as
necessary).
""*Table 1505.1; delete footnote c and replace footnote b with the following:
b. Non-classified roof coverings shall be permitted on buildings of U occupancies having not more than
120 sq. ft. of protected roof area. When exceeding 120 sq. ft. of protected roof area, buildings of U
occupancies may use non-rated non-combustible roof coverings.
s. [delete]
(Reason: Conforms to regional practice affording increased fire protection.)
**Section 1505.7; delete the section
(Reason: Conforms to regional practice. )
~,
**Section 1510.1; add a sentence to read as follows:
1510.1 General. Materials and methods of applications used for recovering or replacing an existing roof
covering shall comply with the requirements of Chapter 15. All individual replacement shingles or shakes
shall be in compliance with the rating required by Table 1505.1.
(text of exception unchanged}
(Reason: Relocated the text to more appropriate place. Previously was footnote "b" to Table 1505.1)
"`"`Section 2901.1; add a sentence to read as follows:
[P] 2901.1 Scope. {existing text to remain} The provisions of this Chapter are meant to work in
coordination with the provisions of Chapter 4 of the International Plumbing Code. Should any conflicts
arise between the two chapters the Building Official shall determine which provision applies
(Reason: Gives building official discretion.)
**Section 2902.1; add a second paragraph to read as follows:
In other than E Occupancies, the minimum number of fixtures in Table 2902.1 may be lowered if
requested in writing, by the applicant stating reasons for a reduced number and approved by the Building
Official.
To allow flexibility for designer to consider
**Table 2902.1; change footnote f to read as follows:
f. Drinking fountains are not required in M Occupancies with an occupant load of 100 or less B
Occupancies with an occupant load of 25 or less and for dining and/or drinking establishments
(Reason: Ad ~ustment meets the needs of specific occupancy types.)
***Section 2902.1.3; add new Section 2902.1.3 to read as follows:
North Central Texas Council of Governments 15 January 21, 20142012 IBC Amendments
2902.1.3 Additional fixtures for food preparation facilities. In addition to the fixtures required in this
Chapter, all food service facilities shall be provided with additional fixtures set out in this section.
2902.1.3.1 Hand washing lavatory. At least one hand washing lavatory shall be provided for use by
employees that is accessible from food preparation, food dispensing and ware washing areas. Additional
hand washing lavatories may be required based on convenience of use by employees.
2902.1.3.2 Service sink. In new or remodeled food service establishments, at least one service sink or
one floor sink shall be provided so that it is conveniently located for the cleaning of mops or similar wet
floor cleaning tool and for the disposal of mop water and similar liquid waste. The location of the service
sink(s) and/or mop sink(s) shall be approved by the <Jurisdiction's> health department.
(Reason: Coordinates Health law requirements with code language for consistent regional practice.)
'`*Section 3006.1; change to read as follows:
3006.1, General. Assess Elevator machine rooms shall be provided. {Remainder unchanged.}
(Reason: An elevator machine room is necessary to provide a protected space for elevator equipment
that is used by the fire service, the disabled, and in the future, building occupant evacuations.)
"*Section 3006.4 {3006.5 if previous amendment adopted}; add a sentence to read as follows and
delete exceptions 1 and 2:
f F13006.4. Machine Rooms and Machinery Spaces: {text unchanged}... Storage shall not be allowed
within the elevator machine room. Provide approved signage at each entry door to the elevator machine
room stating "Elevator Machinery - No Storage Allowed."
(Reason: Firefighter and public safety. This amendment eliminates the shunt trip requirement of the
International Building Code Section 3006.5 for the purpose of elevator passenger and firefighter safety.
This amendment is contingent on the Building Code amendment eliminating the Exceptions to Section
3006.4, such that passive fire barriers for these areas are maintained. This also meets with local practices
in the region.)
***Section 3109.1; change to read as follows:
3109.1 General. Swimming pools shall comply with the requirements of sections 3109.2 through 3109.5
and other applicable sections of this code and complying with applicable state laws.
(Reason: To recognize "state requirements".)
***Section 3401.6 5 Alternative Compliance. Work performed in accordance with the International
Existing Building Code shall be deemed to comply with the provisions of this chapter with prior approval
from the Building Official.
(Reason: Correct ty o and ali n with referenced standards.)
***Section 3401.5 6 Dangerous Conditions. {Remainder unchanged.}
(Reason: Correct typo and align with referenced standards.)
North Central Texas Council of Governments 16 January 21, 20142012 IBC Amendments
Recommended Amendments to the
2012 International Fuel Gas Code
North Central Texas Council of Governments region
The following sections, paragraphs, and sentences of the 2012 International Fuel Gas Code are hereby
amended as follows: Standard type is text from the IFGC. Underlined type is text inserted. ' ~^°~' +"~^~ ~^"
+"^° ?~ d°!°t.°,d t°~+ f •,, 'r~~ A double asterisk at the beginning of a section identifies an amendment
carried over from the 2009 edition of the code and a triple asterisk identifies a new or revised amendment
with the 2012 code.
**Section 101.2
{Local amendments to Section 101.2 maybe necessary to correspond with the State Plumbing
Licensing Law.}
**Section 102.2; add an exception to read as follows:
Exception: Existing dwelling units shall comply with Section 621 2
(Reason: Previous code provisions made unvented heater provisions retroactive except as provided for
in local amendment. This amendment and amendment to IFGC 621.2 better clarify what the code
already states: existing systems may stay unless considered unsafe.)
**Section 102.8; change to read as follows:
102.8 Referenced codes and standards. The codes and standards referenced in this code shall be
those that are listed in Chapter 8 and such codes, when specifically adopted, and standards shall be
considered part of the requirements of this code to the prescribed extent of each such reference. Where
differences occur between provisions of this code and the referenced standards, the provisions of this
code shall apply. Whenever amendments have been adopted to the referenced codes and standards
each reference to said code and standard shall be considered to reference the amendments as well An
reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted
(Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced
codes.)
"*Section 304.10; change to read as follows:
304.10 Louvers and grilles. The required size of openings for combustion, ventilation and dilution air
shall be based on the net free area of each opening. Where the free area through a design of louver,
grille or screen is known, it shall be used in calculating the size opening required to provide the free area
specified. Where the design and free area of louvers and grilles are not known, it shall be assumed that
wood louvers will have 25-percent free area and metal louvers and grilles will have X50-percent free
area. Screens shall have a mesh size not smaller than '/4 inch (6.4 mm). Nonmotorized louvers and grilles
shall be fixed in the open position. Motorized louvers shall be interlocked with the appliance so that they
are proven to be in the full open position prior to main burner ignition and during main burner operation.
Means shall be provided to prevent the main burner from igniting if the louvers fail to open during burner
start-up and to shut down the main burner if the louvers close during operation.
(Reason: This is the generally accepted practice in the region.)
North Central Texas Council of Governments 1 March 2013
2012 IFGC Amendments
**Section 304.11; change #8 to read as follows:
304.11 Combustion air ducts. Combustion air ducts shall comply with all of the following:
1. Ducts shall be constructed of galvanized steel complying with Chapter 6 of the International
Mechanical Code or of a material having equivalent corrosion resistance, strength and rigidity.
Exception: Within dwellings units, unobstructed stud and joist spaces shall not be prohibited
from conveying combustion air, provided that not more than one required fireblock is
removed.
2. Ducts shall terminate in an unobstructed space allowing free movement of combustion air to the
appliances.
3. Ducts shall serve a single enclosure.
4. Ducts shall not serve both upper and lower combustion air openings where both such openings
are used. The separation between ducts serving upper and lower combustion air openings shall
be maintained to the source of combustion air.
5. Ducts shall not be screened where terminating in an attic space.
6. Horizontal upper combustion air ducts shall not slope downward toward the source of combustion
air.
7. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping
installed within a masonry, metal or factory-built chimney shall not be used to supply combustion
air.
Exception: Direct-vent gas-fired appliances designed for installation in a solid fuel-burning
fireplace where installed in accordance with the manufacturer's instructions.
8. Combustion air intake openings located on the exterior of a building shall have the lowest side of
such openings located not less than 12 inches (305 mm) vertically from the adjoining ground level
or the manufacturer's recommendation, whichever is more restrictive.
North Central Texas Council of Governments 2 March 2013
2012 IFGC Amendments
**'`Section 306.3; change to read as follows:
[M] 306.3 Appliances in attics. Attics containing appliances requiring access shall be provided .. .
{bulk of paragraph unchanged} ...side of the appliance. The clear access opening dimensions shall be
a minimum of 20 inches by 30 inches (508 mm by 762 mm), a~ or larger where such dimensions are not
large enough to allow removal of the largest appliance. A walkway to an appliance shall be rated as a
floor as approved by the building official. As a minimum, for access to the attic space provide one of
the following:
1. A permanent stair.
2. A pull down stair with a minimum 300 Ib (136 kg) capacity
3. An access door from an upper floor level.
4. Access Panel may be used in lieu of items 1 2 and 3 with prior approval of the code official due
to building conditions.
Exceptions:
1. The passageway and level service space are not required where the appliance is
capable of being serviced and removed through the required opening.
2. Where the passageway is not less than ... {bulk of section to read the same}.
(Reason: To provide a safe means of accessibility to appliances in attics and to allow for different types
of construction limitations. Consistent with regional amendment to IMC 306.3.)
***Section 306.5; change to read as follows:
[M] 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring
access or appliances are located on an elevated structure or the roof of a building such that personnel will
have to climb higher than 16 feet (4877 mm) above grade to access, ar- a permanent interior or exterior
means of access shall be provided. Permanent exterior ladders providing roof access need not extend
closer than- 12 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment
and appliances' level service space. Such access shall ... {bulk of section to read the same}... on roofs
having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope).... {bulk of section to
read the same}.
(Reason: To assure safe access to roof appliances. Consistent with IMC amendments.)
*'`Section 306.5.1; change to read as follows:
[M] 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service
are installed
on roofs having slopes greater than 4 units vertical in 12 units horizontal and having an edge more than
30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial
cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at
the appliance. The level platform shall be provided on each side of the appliance to which access is
required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any
dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm)
above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm)
sphere and shall comply with the loading requirements for guards specified in the International Building
Code.
(Reason: To assure safe access to roof appliances. Consistent with IMC amendments.)
North Central Texas Council of Governments 3 March 2013
2012 IFGC Amendments
**Section 306; add Section 306.7with exception and subsection 306.7.1 to read as follows:
306.7 Water heaters above ground or floor When the attic roof mezzanine or platform in which a
water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level it shall be
made accessible by a stairway or permanent ladder fastened to the building
Exception: A max 10 gallon water heater (or larger when approved by the code official) is capable of
being accessed through a lav-in ceiling and a water heater is installed is not more than ten (10) feet
(3048 mm) above the ground or floor level and may be reached with a portable ladder
306.7.1. Illumination and convenience outlet. Whenever the mezzanine or platform is not adequately
lighted or access to a receptacle outlet is not obtainable from the main level lighting and a receptacle
outlet shall be provided in accordance with Section 306 3 1
(Reason: To provide more stringent safe access to water heaters. Consistent with regional amendments
to IPC 502.5 and /MC 306.6.)
**Section 401.5; add a second paragraph to read as follows:
Both ends of each section of medium pressure corrugated stainless steel tubing (CSST) shall identify its
operating pas pressure with an approved tag The taps are to be composed of aluminum or stainless
steel and the following wording shall be stamped into the taq~
"WARNING
1/2 to 5 psi pas pressure
Do Not Remove"
(Reason: To protect homeowners and plumbers.)
**Section 402.3; add an exception to read as follows:
Exception: Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2" (18 EHD)
(Reason: Pipe less than 7/2" has a history in this region of causing whistling.)
***Section 404.12; change to read as follows:
404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of ~
18 inches (385 458 mm) top of pipe below grade, .
(Reason: To provide increased protection to piping systems and address reference number change.)
"**Section 404.12.1; change to read as follows:
404.12.1 Individual outside appliances. Individual lines to outside lights, grills or other appliances shall
be installed a minimum of ~ 72 inches (203 mm) top of pipe below finished grade, provided that such
installation is approved and is installed in locations not susceptible to physical damage.
(Reason: To provide increased protection to piping systems and address reference number change.)
North Central Texas Council of Governments 4 March 2013
2012 IFGC Amendments
**Section 406.1; change to read as follows:
406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and
pressure tested to determine that the materials, design, fabrication, and installation practices comply with
the requirements of this code. The permit holder shall make the applicable tests prescribed in Sections
406.1.1 through 406.1.5 to determine compliance with the provisions of this code The permit holder shall
give reasonable advance notice to the code official when the piping system is ready for testing The
equipment, material, power and labor necessary for the inspections and test shall be furnished by the
permit holder and the permit holder shall be responsible for determining that the work will withstand the
test pressure prescribed in the following tests.
(Reason: To utilize language used in the IPC regarding who is responsible for testing procedures.)
**Section 406.4; change to read as follows:
406.4 Test pressure measurement. Test pressure shall be measured with a monometer or with a
pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused
by leakage during the pressure test period. The source of pressure shall be isolated before the pressure
tests are made.
(Reason: To require the use of more accurate diaphragm gauges. Spring gauges do not provide
accurate measurement below approximately 17 psig.)
**Section 406.4.1; change to read as follows:
406.4.1 Test pressure. The test pressure to be used shall be no less than ~ ~ ~~ +~^^^~ +"^ ^~^^^ ^~
maximum werlFing~ressare, " + ^ ~^~ +" ' 3 psig (20 kPa gauge), or at the discretion of the Code
Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury
measured with a manometer or slope gauge ~ .
.For tests
requiring a pressure of 3 psig diaphragm gauges shall utilize a dial with a minimum diameter of three and
one half inches (3'/z"), a set hand 1/10 pound incrementation and pressure range not to exceed 6 psi for
tests reauirinq a pressure of 3 psig For tests requiring a pressure of 10 psig diaphragm gauges shall
utilize a dial with a minimum diameter of three and one-half inches (3 %") a set hand a minimum of 2/10
pound incrementation and a pressure range not to exceed 20 psi For welded piping and for piping
carrymQ pas at pressures m excess of fourteen (14) inches water column pressure (3 48 kPa) (1/2 psi)
and less than 200 inches of water column pressure (52 2 kPa) (7 5 psi) the test pressure shall not be
less than ten (10) pounds per sauare inch (69 6 kPa) For piping carrying pas at a pressure that exceeds
200 inches of water column (52.2 kPa) (7.5 psi) the test pressure shall be not less than one and one half
times the proposed maximum working pressure
(Reason: To provide for lesser pressures to coordinate with the use of more accurate diaphragm
gauges.)
**Section 406.4.2; change to read as follows:
406.4.2 Test duration. Test duration shall be held for a length of time satisfactory to the Code Official
but in no case for less than fifteen (15) minutes For welded piping and for piping carrying pas at
pressures in excess of fourteen (14) inches water column pressure (3 48 kPa) the test duration shall be
North Central Texas Council of Governments 5 March 2013
2012 IFGC Amendments
held for a length of time satisfactory to the Code Official but in no case for less than thirty (30) minutes
(Delete remainder of section. )
(Reason: To comply with accepted regional practices.)
**Section 409.1; add Section 409.1.4 to read as follows:
409.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST)
Aping systems shall be supported with an approved termination fitting or equivalent support suitable for
the size of the valves, of adequate strength and quality and located at intervals so as to prevent or damp
out excessive vibration but in no case greater than 12-inches from the center of the valve Supports shall
be installed so as not to interfere with the free expansion and contraction of the system's piping fittings
and valves between anchors. All valves and supports shall be designed and installed so they will not be
disengaged by movement of the supporting piping_
(Reason: To provide proper security to CSST valves. These standards were established in this region in
1999 when CSST was an emerging technology.)
**Section 410.1; add a second paragraph and exception to read as follows:
Access to regulators shall comply with the reauirements for access to appliances as specified in Section
306.
Exception: A passageway or level service space is not required when the regulator is capable of
being serviced and removed through the required attic opening
(Reason: To require adequate access to regulators.)
**Section 621.2; add exception as follows:
621.2 Prohibited use. One or more unvented room heaters shall not be used as the sole source of
comfort heating in a dwelling unit.
Exception: Existing approved unvented heaters may continue to be used in dwelling units in
accordance with the code provisions in effect when installed when approved by the Code Official
unless an unsafe condition is determined to exist as described in Section 108 7
(Reason: Gives code official discretion.)
**Section 624.1.1; change to read as follows:
624.1.1 Installation requirements. The requirements for water heaters relative to access, sizing, relief
valves, drain pans and scald protection shall be in accordance with the International Plumbing Code.
(Reason: To clarify installation requirements. Also corresponds with amendments regarding water heater
access.)
END
North Central Texas Council of Governments 6 March 2013
2012 IFGC Amendments
Recommended Amendments to the
2012 International Energy Conservation Code
North Central Texas Council of Governments Region
(Climate Zone 3 of the IECC)
The following sections, paragraphs, and sentences of the 2012 International Energy Conservation Code
(IECC) are hereby amended as follows: Standard type is text from the IECC. Underlined type is text
inserted. I p ;~°,'~ +hrn~ ~yh +~in^ ;~ ,+ ~o+o,+ + + c ~_~^ A double (*") asterisk at the beginning of a section
identifies an amendment carried over from the 2009 edition of the code and a triple (*"*) asterisk identifies
a new or revised amendment with the 2009 code.
Note: Historically NCTCOG has limited Chapter 1 amendments in order to allow each city to insert their
local policies and procedures. We now have suggested certain items to be brought to the attention of
cities considering adoption of the code that may be of concern to several jurisdictions. It is still intended
to be discretionary to each city to determine which Chapter 1 amendments to include.
The 2012 IECC contains separate provisions for commercial buildings (preceded by "C" for Commercial)
and for residential buildings (preceded by "R" for residential buildings) 3 stories or less. Each set of
provisions are separately applied to buildings within their respective scope. Each set of provisions also
contains a Scope and Administration chapter, a Definitions chapter, a General Requirements chapter and
a chapter containing energy efficiency requirements applicable to building within their respective scope.
Recommended amendments that match sections in each of the respective provisions ("C" and "R") are
written to represent both sections rather than duplicating the recommended amendment in this document.
Sections N1101.2 through N1105 of the 2012 International Residential Code (IRC) are noted to be
extracted from the 2012 IECC. The Building and Residential Advisory Board (BRAB) recommends
amending Chapter 11 [RE] ENERGY EFFICIENCY of the 2012 IRC to refer to the residential provisions of
the 2012 IECC.
As of the date of the recommendations the State Energy Conservation Office (SEGO) has not adopted
the 2012 IECC. Consequently the recommended amendments to the 2012 IECC have been analyzed for
stringency with the current Texas Building Energy Performance Standards (TBEPS) which is the 2009
Edition of the IECC and the energy provisions of the IRC. Some amendments below are noted that
if/when SEGO does by rule adopt the 2012 IECC as the TBEPS, the proposed amendment would be
deemed less stringent and therefore would not be considered a recommended amendment.
**Section C101.4.2 and R101.4.2; change to read as fo//ows:
C101.4.2/R101.4.2 Historic Buildings. Any building or structure that is listed in the State or National
Register of Historic Places; designated as a historic property under local or state designation law or
survey; certified as a contributing resource with a National Register listed or locally designated historic
district; or with an opinion or certification that the property is eligible to be listed on the National or State
Registers of
Historic Places either individually or as a contributing building to a historic district by the State Historic
Preservation Officer of the Keeper of the National Register of Historic Places, arm^~^m^+ +•^^, shall
comply with all of the provisions of this code.
Exception: Whenever a provision or provisions shall invalidate or jeopardize the historical
designation or listing, that provision or provisions may be exempted
(Reason: This is less restrictive than the legislative mandates. It is reasonable to expect compliance with
duct sealing, replacement lighting and the installation of insulation, for example, when possible.)
North Central Texas Council of Governments 1 March 2013
2012 IECC Amendments
**Section C102/R102; add Section C102.1.2 and R102.1.2 to read as follows:
C102.1.2/R102.1.2 Alternative compliance. A building certified by a national state or local accredited
energv efficiencv program and determined by the Energy Systems Laboratory to be in compliance with
the energy efficiencv requirements of this section may at the option of the Code Official be considered in
compliance. The United States Environmental Protection Agency's Eneray Star Program certification of
energv code eauivalencv shall be considered in compliance
(Reason: this amendment is added to allow alternative compliance in accordance with Texas HB 1365,
78th Legislature.)
**Section C202 and R202; add the following definition:
GLAZING AREA. Total area of the glazed fenestration measured using the rough opening and including
sash, curbing or other framing elements that enclose conditioned space Glazing area includes the area
of glazed fenestration assemblies in walls bounding conditioned basements For doors where the
daylight opening area is less that 50 percent of the door area the glazing area is the daylight opening
area. For all other doors the Glazing area is the rough opening area for the door including the door and
the frame.
(Reason: Since the window to floor area ratios have been added to the prescriptive tables, it is necessary
to define glazing area.)
***Section R402.2.2; amend the section to read as follows:
R402.2.2 Ceilings without attic spaces. Where Section R402.1.1 would require insulation levels above
R-30 and the design of the roof/ceiling assembly does not allow sufficient space for the required
insulation, the minimum required insulation for such roof/ceiling assemblies shall be R-30. This reduction
of insulation from the requirements of Section R402.1.1 shall be limited to 500 square feet (46 m2) er~A
nnrnon# of +hc tctul :^°~~~°+~~ ^~;~;^^ ~~~~ ~~ h ~ .This reduction shall not apply to the U -factor
alternative approach in Section R402.1.3 and the total UA alternative in Section R402.1.4.
(Reason: Retains the current 2009 language to eliminate confusion and limit the area to 500 square feet
maximum)
"`** Table R402.1.1 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT; Amend
by changing the WOOD FRAME WALL R-VALUE for CLIMATE ZONE 3 to read as follows:
13
(Reason: Retain the values in the 2009 code.)
If/when SECO does by rule adopt the 2012 IECC, this proposed amendment would be deemed less
stringent and therefore would not be considered a recommended amendment.
North Central Texas Council of Governments 2 March 2013
2012 IECC Amendments
*** Table R402.1.3 EQUIVALENT U-FACTORS; Amend by changing the WOOD FRAME WALL U-
FACTOR for CLIMATE ZONE 3 to read as follows:
0.082
(Reason: Retain the values in the 2009 code.)
If/when SECO does by rule adopt the 2012 IECC, this proposed amendment would be deemed less
stringent and therefore would not be considered a recommended amendment.
***R402.4.1.2 Testing; Add a last paragraph to read as follows:
Testing may only be performed by individuals that are certified HERS Raters or Rating Field Inspectors by
RESNET or Performance Verification Technicians certified by Texas HERO, or other certifications as may
be approved by the building official. The certified individuals must be an independent third-party entity,
and may not be employed; or have any financial interest in the company that constructs the structure.
(Reason: The 2012 International Residential Code (IRC) and International Energy Conservation Code
(IECC) include enhanced emphasis on envelope infiltration and duct leakage. Significant changes in the
residential energy requirements include more frequent requirement of performance testing for leakage.
Residential Duct systems must be tested unless all ducts and equipment are located within the
conditioned space. Envelope testing is required to demonstrate compliance with maximum allowable
leakage rate unless a detailed air barrier and insulation inspection has been performed to field verify
component criteria. This language puts the regulatory authority on notice that the testing requires
specialized credentials and establishes a conflict of interest baseline).
***Section R402.4.1.2 Testing; modify the first paragraph to read as follows:
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage
rate of not exceeding 5 air changes per hour in OlimatP Zones 1 and 2, °^~ ~ ~~~ nh.,,,n h
Climate Zones 3 tk~e~k--~. {Remainder of text unchanged}
(Reason: The 2012 IECC will require mandatory door blower testing on each dwelling unit. The visual
inspection is no longer an option to performance testing. This change will give some time for those
builders not currently using a performance approach to adapt construction practices.)
If/when SECO does by rule adopt the 2012 IECC, this proposed amendment would be deemed less
stringent and therefore would not be considered a recommended amendment.
***R403.2.2 Sealing (Mandatory); Add a last paragraph to read as follows:
Testing may only be performed by individuals that are certified HERS Raters or Rating Field Inspectors by
RESNET or Performance Verification Technicians certified by Texas HERO, or other certifications as may
be approved by the building official. The certified individuals must be an independent third-party entity,
and may not be employed; or have any financial interest in the company that installed the duct system.
North Central Texas Council of Governments 3 March 2013
2012 IECC Amendments
(Reason: The 2012 International Residential Code (IRC) and International Energy Conservation Code
(IECC) include enhanced emphasis on envelope infiltration and duct leakage. Significant changes in the
residential energy requirements include more frequent requirement of performance testing for leakage.
Residential Duct systems must be tested unless all ducts and equipment are located within the
conditioned space. Envelope testing is required to demonstrate compliance with maximum allowable
leakage rate unless a detailed air barrier and insulation inspection has been performed to field verify
component criteria. This language puts the regulatory authority on notice that the testing requires
specialized credentials and establishes a conflict of interest baseline).
*** Section R403.2,2; Amend to read as follows:
R403.2.3 Building cavities (Mandatory). Building framing cavities shall not be used as supply ducts aad
mss. Building framing wall cavities in the exterior thermal envelope shall not be used as return ducts
(Reason: Continue the practice in the regions and to insure that the building thermal envelope is not
compromised.)
**Section C402.2.9/R402.2; Add Section C402.2.9 and R402.2.13 to read as follows:
Section C402.2.9/R402.2 Insulation installed in walls. To insure that insulation remains in place
insulation batts installed in walls shall be totally secured by an enclosure on all sides consisting of framing
lumber, aypsum, sheathing wood structural panel sheathing netting or other eauivalent material
approved by the building official.
(Reason: This will increase the performance of the insulation by ensuring that the batt insulation stays in
place.)
***Section R405.6.2; add the following sentence to the end of paragraph:
Acceptable performance software simulation tools may include, but are not limited to, REM
Rate "', Energy Gauge and IC3. Other performance software programs accredited by RESNET
BESTEST and having the ability to provide a report as outlined in R405.4.2 may also be
deemed acceptable performance simulation programs and may be considered by the building
official.
(Reason: These performance software tools are accredited by RESNET at the time of recommendation.)
***Section C101.4.3 Additions, alterations, renovations or repairs; add exception #9 to read as
follows:
9. Replacement of existing fenestration, provided, however, that the area of the replacement fenestration
does not exceed 25% of the total fenestration area of an existing building and that the U-factor and SHGC
will be equal to or lower than before the fenestration replacement.
(Reason: Provide some level of consideration for existing buildings, matches ASHRAE 90.1-2010
Exception "g" to Section 5.1.3.)
North Central Texas Council of Governments 4 March 2013
2012 IECC Amendments
If/when SECO does by rule adopt the 2012 IECC, this proposed amendment would be deemed less
stringent and therefore would not be considered a recommended amendment.
END
North Central Texas Council of Governments 5 March 2013
2012 IECC Amendments
Recommended Amendments to the
2012 International Fuel Gas Code
North Central Texas Council of Governments region
The following sections, paragraphs, and sentences of the 2012 International Fuel Gas Code are hereby
amended as follows: Standard type is text from the IFGC. Underlined type is text inserted. ~ ~^°~+ +hrn,,,.h
+~~^° :~ '~~!~t°'~ t~~t fr~m,, _,r~ A double asterisk at the beginning of a section identifies an amendment
carried over from the 2009 edition of the code and a triple asterisk identifies a new or revised amendment
with the 2012 code.
**Section 101.2
{Local amendments to Section 101.2 maybe necessary to correspond with the State Plumbing
Licensing Law.}
**Section 102.2; add an exception to read as follows:
Exception: Existing dwelling units shall comply with Section 621.2
(Reason: Previous code provisions made unvented heater provisions retroactive except as provided for
in local amendment. This amendment and amendment to IFGC 621.2 better clarify what the code
already states: existing systems may stay unless considered unsafe.)
**Section 102.8; change to read as follows:
102.8 Referenced codes and standards. The codes and standards referenced in this code shall be
those that are listed in Chapter 8 and such codes, when specifically adopted, and standards shall be
considered part of the requirements of this code to the prescribed extent of each such reference. Where
differences occur between provisions of this code and the referenced standards, the provisions of this
code shall apply. Whenever amendments have been adopted to the referenced codes and standards
each reference to said code and standard shall be considered to reference the amendments as well An
reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted
(Reason: Legal wording to recognize locally adopted codes and amendments adopted with referenced
codes.)
**Section 304.10; change to read as follows:
304.10 Louvers and grilles. The required size of openings for combustion, ventilation and dilution air
shall be based on the net free area of each opening. Where the free area through a design of louver,
grille or screen is known, it shall be used in calculating the size opening required to provide the free area
specified. Where the design and free area of louvers and grilles are not known, it shall be assumed that
wood louvers will have 25-percent free area and metal louvers and grilles will have X50-percent free
area. Screens shall have a mesh size not smaller than %< inch (6.4 mm). Nonmotorized louvers and grilles
shall be fixed in the open position. Motorized louvers shall be interlocked with the appliance so that they
are proven to be in the full open position prior to main burner ignition and during main burner operation.
Means shall be provided to prevent the main burner from igniting if the louvers fail to open during burner
start-up and to shut down the main burner if the louvers close during operation.
(Reason: This is the generally accepted practice in the region.)
North Central Texas Council of Governments 1 March 2013
2012 IFGC Amendments
**Section 304.11; change #8 to read as follows:
304.11 Combustion air ducts. Combustion air ducts shall comply with all of the following:
1. Ducts shall be constructed of galvanized steel complying with Chapter 6 of the International
Mechanical Code or of a material having equivalent corrosion resistance, strength and rigidity.
Exception: Within dwellings units, unobstructed stud and joist spaces shall not be prohibited
from conveying combustion air, provided that not more than one required fireblock is
removed.
2. Ducts shall terminate in an unobstructed space allowing free movement of combustion air to the
appliances.
3. Ducts shall serve a single enclosure.
4. Ducts shall not serve both upper and lower combustion air openings where both such openings
are used. The separation between ducts serving upper and lower combustion air openings shall
be maintained to the source of combustion air.
5. Ducts shall not be screened where terminating in an attic space.
6. Horizontal upper combustion air ducts shall not slope downward toward the source of combustion
air.
7. The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping
installed within a masonry, metal or factory-built chimney shall not be used to supply combustion
air.
Exception: Direct-vent gas-fired appliances designed for installation in a solid fuel-burning
fireplace where installed in accordance with the manufacturer's instructions.
8. Combustion air intake openings located on the exterior of a building shall have the lowest side of
such openings located not less than 12 inches (305 mm) vertically from the adjoining ground level
or the manufacturer's recommendation, whichever is more restrictive.
(Reason: To recognize the manufacturer's installation requirements.)
**Section 305.5; de/ete the section.
(Reason: This provision does not reflect standard practice in this area. Consistent with regional
amendment to IMC 304.6.)
North Central Texas Council of Governments 2 March 2013
2012 IFGC Amendments
*Section 306.3; change to read as follows:
[M] 306.3 Appliances in attics. Attics containing appliances requiring access shall be provided .. .
{bulk of paragraph unchanged} ...side of the appliance. The clear access opening dimensions shall be
a minimum of 20 inches by 30 inches (508 mm by 762 mm), a+~ or larger where such dimensions are not
large enough to allow removal of the largest appliance. A walkway to an appliance shall be rated as a
floor as approved by the building official. As a minimum, for access to the attic space provide one of
the following:
1. A permanent stair.
2. A pull down stair with a minimum 300 Ib (136 kq) capacity
3. An access door from an upper floor level.
4. Access Panel may be used in lieu of items 1 2 and 3 with prior approval of the code official due
to building conditions.
Exceptions:
1. The passageway and level service space are not required where the appliance is
capable of being serviced and removed through the required opening.
2. Where the passageway is not less than ... {bulk of section to read the same}.
(Reason: To provide a safe means of accessibility to appliances in attics and to allow for different types
of construction limitations. Consistent with regional amendment to IMC 306.3.)
***Section 306.5; change to read as follows:
[M] 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring
access or appliances are located on an elevated structure or the roof of a building such that personnel will
have to climb higher than 16 feet (4877 mm) above grade to access, an a permanent interior or exterior
means of access shall be provided. Permanent exterior ladders providing roof access need not extend
closer than- 12 feet (2438 mml to the finish grade or floor level below and shall extend to the equipment
and appliances' level service space. Such access shall ... {bulk of section to read the same}... on roofs
having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope).... {bulk of section to
read the same}.
(Reason: To assure safe access to roof appliances. Consistent with IMC amendments.)
"*Section 306.5.1; change to read as follows:
[M] 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service
are installed
on roofs having slopes greater than 4 units vertical in 12 units horizontal and having an edge more than
30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial
cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at
the appliance. The level platform shall be provided on each side of the appliance to which access is
required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any
dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm)
above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm)
sphere and shall comply with the loading requirements for guards specified in the International Building
Code.
(Reason: To assure safe access to roof appliances. Consistent with IMC amendments.)
North Central Texas Council of Governments 3 March 2013
2012 IFGC Amendments
**Section 306; add Section 306.7with exception and subsection 306.7.1 to read as follows:
306.7 Water heaters above ground or floor. When the attic roof mezzanine or platform in which a
water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level it shall be
made accessible by a stairway or permanent ladder fastened to the building_
Exception: A max 10 Gallon water heater (or larger when approved by the code official is capable of
being accessed through a lav-in ceiling and a water heater is installed is not more than ten (10) feet
(3048 mm) above the ground or floor level and may be reached with a portable ladder
306.7.1. Illumination and convenience outlet. Whenever the mezzanine or platform is not adeauately
lighted or access to a receptacle outlet is not obtainable from the main level lighting and a receptacle
outlet shall be provided in accordance with Section 306 3 1
(Reason: To provide more stringent safe access to water heaters. Consistent with regional amendments
to IPC 502.5 and IMC 306.6.)
**Section 401.5; add a second paragraph to read as follows:
Both ends of each section of medium pressure corrugated stainless steel tubing (CSST) shall identify its
operating pas pressure with an approved tap. The taps are to be composed of aluminum or stainless
steel and the following wording shall be stamped into the tag
"WARNING
1/2 to 5 psi pas pressure
Do Not Remove"
(Reason: To protect homeowners and plumbers.)
**Section 402.3; add an exception to read as follows:
Exception: Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2" (18 EHD)
(Reason: Pipe less than 1/2" has a history in this region of causing whistling.)
**'`Section 404.12; change to read as follows:
404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of ~
18 inches (3A~ 458 mm) top of pipe below grade, .
(Reason: To provide increased protection to piping systems and address reference number change.)
***Section 404.12.1; change to read as follows:
404.12.1 Individual outside appliances. Individual lines to outside lights, grills or other appliances shall
be installed a minimum of S 12 inches (203 mm) top of pipe below finished grade, provided that such
installation is approved and is installed in locations not susceptible to physical damage.
(Reason: To provide increased protection to piping systems and address reference number change.)
North Central Texas Council of Governments 4 March 2013
2012 IFGC Amendments
**Section 406.1; change to read as follows:
406.1 General. Prior to acceptance and initial operation, all piping installations shall be inspected and
pressure tested to determine that the materials, design, fabrication, and installation practices comply with
the requirements of this code. The permit holder shall make the applicable tests prescribed in Sections
406.1.1 through 406.1.5 to determine compliance with the provisions of this code The permit holder shall
a~ve reasonable advance notice to the code official when the piping system is ready for testing The
equipment, material, power and labor necessary for the inspections and test shall be furnished by the
permit holder and the permit holder shall be responsible for determining that the work will withstand the
test pressure prescribed in the following tests
(Reason: To utilize language used in the IPC regarding who is responsible for testing procedures.)
**Section 406.4; change to read as follows:
406.4 Test pressure measurement. Test pressure shall be measured with a monometer or with a
pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused
by leakage during the pressure test period. The source of pressure shall be isolated before the pressure
tests are made.
(Reason: To require the use of more accurate diaphragm gauges. Spring gauges do not provide
accurate measurement below approximately 17 psig.)
*"Section 406.4.1; change to read as follows:
406.4.1 Test pressure. The test pressure to be used shall be no less than 1 1!?ti;;;ec ±..",~ ^r^^^~~~
p. ~ .. ~+...,~.v
3 psig (20 kPa gauge), or at the discretion of the Code
Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury,.
measured with a manometer or slope gauge ~ .
.For tests
requiring a pressure of 3 psig diaphragm gauges shall utilize a dial with a minimum diameter of three and
one half inches (3 %"), a set hand 1/10 pound incrementation and pressure range not to exceed 6 psi for
tests requiring a pressure of 3 psig For tests reauirinq a pressure of 10 Asia diaphragm gauges shall
utilize a dial with a minimum diameter of three and one-half inches (3 '/") a set hand a minimum of 2/10
pound incrementation and a pressure range not to exceed 20 psi For welded piping and for piping
carrying pas at pressures in excess of fourteen (14) inches water column pressure (3 48 kPa) (1/2 psi)
and less than 200 inches of water column pressure (52 2 kPa) (7 5 psi) the test pressure shall not be
less than ten (10) pounds per square inch (69 6 kPa) For piping carrying gas at a pressure that exceeds
200 inches of water column (52.2 kPa) (7 5 psi) the test pressure shall be not less than one and one half
times the proposed maximum working pressure
(Reason: To provide for lesser pressures to coordinate with the use of more accurate diaphragm
gauges.)
**Section 406.4.2; change to read as follows:
406.4.2 Test duration. Test duration shall be held for a length of time satisfactory to the Code Official
but in no case for less than fifteen (15) minutes For welded piping and for piping carrying gas at
pressures in excess of fourteen (14) inches water column pressure (3 48 kPa) the test duration shall be
North Central Texas Council of Governments 5 March 2013
2012 IFGC Amendments
held for a length of time satisfactory to the Code Official but in no case for less than thirty (30) minutes
(Delete remainder of section.
(Reason: To comply with accepted regional practices.)
**Section 409.1; add Section 409.1.4 to read as follows:
409.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST)
piping systems shall be supported with an approved termination fitting or equivalent support suitable for
the size of the valves of adeauate strength and quality and located at intervals so as to prevent or damp
out excessive vibration but in no case greater than 12-inches from the center of the valve Supports shall
be installed so_as not to interfere with the free expansion and contraction of the system's piping fittings
and valves between anchors. All valves and supports shall be designed and installed so they will not be
disengaged by movement of the supporting piping
(Reason: To provide proper security to CSST valves. These standards were established in this region in
1999 when CSST was an emerging technology.)
**Section 410.1; add a second paragraph and exception to read as follows:
Access to reaulators shall comply with the reauirements for access to appliances as specified in Section
306.
Exception: A passageway or level service space is not required when the regulator is capable of
being serviced and removed through the required attic opening
(Reason: To require adequate access to regulators.)
*'`Section 621.2; add exception as follows:
621.2 Prohibited use. One or more unvented room heaters shall not be used as the sole source of
comfort heating in a dwelling unit.
Exception: Existing approved unvented heaters may continue to be used in dwelling units in
accordance with the code provisions in effect when installed when approved by the Code Official
unless an unsafe condition is determined to exist as described in Section 108.7.
(Reason: Gives code official discretion.)
**Section 624.1.1; change to read as follows:
624.1.1 Installation requirements. The requirements for water heaters relative to access, sizing, relief
valves, drain pans and scald protection shall be in accordance with the International Plumbing Code.
(Reason: To clarify installation requirements. Also corresponds with amendments regarding water heater
access.)
END
North Central Texas Council of Governments 6 March 2013
2012 IFGC Amendments