HomeMy Public PortalAboutOutsideFoulwaterDropManholeA B SECTION C—C CT NOTES: SECTION A —A 1) THE MINIMUM INSIDE DIAMETER FOR THE BASE AND RISER SECTIONS SHALL BE 42" FOR 8" DIAMETER SANITARY SEWERS AND A MINIMUM INSIDE DIAMETER OF 48" FOR ALL SANITARY AND COMBINED SEWERS LARGER THAN 8" DIAMETER. 2) NEW OUTSIDE DROP ON EXISTING MANHOLE REQUIRES THAT THE FLOWLINE OF THE NEW DROP PIPE ELBOW BE CONSTRUCTED AT THE SAME ELEVATION AS THE SPRINGLINE OF THE EXISTING SEWER MAIN AT THE CENTER OF THE EXISTING MANHOLE. A CLASS "A" CONCRETE FILLET AND INVERT SHALL BE CONSTRUCTED FOR DROP PIPE. 3) DIAMETER OF DROP PIPE FOR COMBINED SEWERS AND SANITARY SEWERS IS SAME AS INCOMING 8", 10" OR 12" PIPE SEWER UNLESS OTHERWISE SHOWN ON PROJECT PLANS. FOR SEWERS 15" THROUGH 24", A DROP IS NOT TO BE USED. RATHER, CONNECT TO MANHOLE AT OR WITHIN 24" ABOVE IT'S FLOWLINE. 4) IF EXCAVATED SPACE OUTSIDE OF DROP PIPE EXCEEDS ONE (1) FOOT, PROVIDE 6" CLASS "A" CONCRETE ENCASEMENT ON INCOMING LINE FROM WALL OF MANHOLE TO A MINIMUM OF TWO (2) FEET INTO UNDISTURBED EARTH WITH A MINIMUM OF 4- #4 REBARS FOR LENGTH OF ENCASEMENT OR INSTALL ONE (1) LENGTH OF D.I.P. FROM "TEE" FITTING INTO UNDISTURBED EARTH. A APPROVED PATENTED COMPRESSION TYPE JOINT FOR PRECAST MANHOLE AND WATER STOP FOR BRICK MANHOLE. REMOVABLE WATERTIGHT PLUG. "FLARED -LEG BRACK-IT" (D021 OR EQUAL) ATTACHED WITH 3/8"x 3" STAINLESS STEEL BOLT WITH APPROVED ANCHOR. (NOT THRU JOINT) LINE OF ACTUAL EXCAVATION SEE NOTE 4) COMPACTED CRUSHED LIMESTONE 6" 6" MIN. DETAIL 5% MAX SLOPE 12" MAX. 3/4' STAINLESS STEEL BAND. MIN. 3 BANDS, MAX. 3' SPACING. "A" FILLETMk r =.11MILWASINAIMME SECTION B—B OUTSIDE FOULWATER DROP MANHOLE METROPOLITAN ST. LOUIS SEWER DISTRICT Standard Details of Sewer Construction Dr. S.A.M. Ch. P.W.S. 2009 SHEET 16