HomeMy Public PortalAboutOrdinance 11-9461 1 ORDINANCE NO. 11 -946 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF TEMPLE CITY AMENDING SECTION 3100 OF THE TEMPLE CITY MUNICIPAL CODE AND ADOPTING THE CONSOLIDATED FIRE PROTECTION DISTRICT OF LOS ANGELES COUNTY FIRE CODE, RATIFYING THE MORE RESTRICTIVE BUILDING STANDARDS CONTAINED IN THAT CODE, AND DELEGATING ENFORCEMENT OF THE FIRE CODE IN THE CITY TO THE FIRE CHIEF. WHEREAS, the City of Temple City lies within the jurisdictional boundaries of the Consolidated Fire Protection District of Los Angeles County (District); and WHEREAS, the District has responsibility for fire protection within said jurisdictional boundaries; and WHEREAS, the County Board of Supervisors, acting as the Governing Body of the District did on November 30, 2010 adopt amendments to the District Fire Code by adopting by reference, with certain changes and amendments, the 2010 Edition of the California Fire Code and the 2009 edition of the International Fire Code; and WHEREAS, as allowed by state law, the District Fire Code contains local amendments that constitute more restrictive building standards relating to fire and panic safety than those adopted by the State Fire Marshal and contained in the California Building Standards Code; and WHEREAS, pursuant to Section 13869.7(c) of the California Health and Safety Code, local amendments containing such more restrictive building standards are not effective within the jurisdictional boundaries of the City until ratified by the City Council; and WHEREAS, it is the intention of the City to amend Section 3100 of the Temple City Municipal Code to reflect the changes to the District Fire Code adopted by its Governing Board on November 30, 2010, including the ratification of all of the more restrictive fire and panic safety standards; NOW, THEREFORE, the City Council of the City of Temple City hereby ordains as follows: SECTION 1. Section 3100 of the Temple City Municipal Code is hereby amended to read as follows: "3100: ADOPTION: The City of Temple City hereby adopts the Consolidated Fire Protection District of Los Angeles County (District) Fire Code as the Fire Code for the City of Temple City. Said District Fire Code is codified in Title 32 of the Los Angeles County Code." SECTION 2. The City Council hereby ratifies the building standards relating to fire and panic safety adopted by the District in Ordinance No. 2010 -0060 that are more stringent than those building standards adopted by the State Fire Marshal and contained in the California Building Standards Code. The District's findings in support of the more stringent building standards are attached to this Ordinance as Exhibit "A." Ordinance No. 11 -946 Page 2 SECTION 3. The City Clerk is instructed to file a copy of this Ordinance with the California Department of Housing and Community Development, Division of Codes and Standards, 1803 3rd Street, Room 260, Sacramento, California 95811 and a copy to the Consolidated Fire Protection District of Los Angeles County, Attn: Chief Roy Dull, Fire Marshall, 5823 Rickenbacker Road, Commerce, California 90040. SECTION 4. Adoption of this Ordinance is exempt from the California Environmental Quality Act (CEQA) in that it can be seen with certainty that there is no possibility that the ordinance may have a significant effect on the environment pursuant to State CEQA Guidelines Section 15061(b)(3). The adoption of the proposed ordinance is covered by the general rule that CEQA applies only to projects that have the potential for causing a significant effect on the environment. The adoption of the proposed ordinance does not have such potential. SECTION 5. The City hereby delegates the authority to enforce the District Fire Code, including the more restrictive building standards contained therein, to the District Fire Chief. SECTION 6. The City Clerk shall certify to the passage and adoption of this Ordinance and to its approval by the Mayor and shall cause the same to be published according to law. SIGNED AND ADOPTED on the 6th day of September, 2011. ATTEST: City Clerk 1 LeNcit 1 I, City Clerk of the City of Temple City, do hereby certify that the foregoing Ordinance, being Ordinance No. 11 -946, was introduced at the regular meeting of the City Council of the City of Temple City held on the 16th day of August, 2011 and was duly adopted by said Council at their regular meeting held on the 6th of September, 2011 by the following vote: AYES: Councilmember -Blum, Sternquist, Vizcarra, Chavez NOES: Councilmember -None ABSENT: Councilmember -Yu ABSTAIN: Councilmember -None rz geo-y.,6Luel City Cler Ordinance No. 11 -946 Page 3 Exhibit A - Section 166 from Ordinance Number 2010 -0060 Adopted by the Los Angeles County Board of Supervisors on November 30, 2010. SECTION 166. Findings in Support of Adoption of More Restrictive Building Standards. The provisions of this ordinance contain various changes, modifications, and additions to the 2010 California Fire Code. Some of those changes are administrative in nature in that they do not constitute changes or modifications to requirements contained in the building standards adopted by the State Fire Marshall and published in the California. Building Standards Code. Pursuant to Health and Safety Code sections 17958.5, 17958.7, and 189415, the Board of Supervisors hereby expressly finds and determines that all of the changes and modifications to requirements contained in the building standards published in the California Building Standards Code, contained in this ordinance, which are not administrative in nature, are reasonably: necessary because of local climatic, geological, or topographical conditions in the County of Los, Angeles and in the Consolidated Fire Protection District of Los Angeles County. This expressed . finding is supported and based upon the following more specific determinations: CLIMATIC - The County of Los Angeles is located in an area subject to climatic conditions with long periods of low humidity and hot weather, combined with unpredictable seasonal high winds (Santa Ana wind conditions), resulting in increased exposure to fire risk. This combination of events creates an environment that is conducive to rapidly spreading fires. Control of such fires requires rapid response. With the time that is required to deal with potential obstacles from the wind, such as fallen trees, street lights, and utility poles, in addition to the time required to climb 75 feet vertically up flights of stairs, the ability to respond rapidly is negatively impacted. Additionally, there is a significant increase in the amount of wind at 60 feet above the ground. Use of aerial -type fire fighting apparatus above this height would place rescue personnel at increased risk of injury. High winds, will also cause burning embers to become airborne resulting in the rapid spread of a fire to nearby structures. Immediate containment of a fire is the Ordinance No. 11 -946 Page 4 only method by which it can be controlled during high wind conditions. In high fire severity zones, a unique combination of low humidity, strong winds, and dry vegetation exists. GEOLOGICAL - The County of Los Angeles is located in the middle of the seismically active area identified as Seismic Zone 4. The viability of the public water system would be questionable at best after a major seismic event. Tall buildings would become vulnerable to uncontrolled fires due to a lack of available water and an inability to pump sufficient quantities of any available water to floors above the 55 -foot level. A severe seismic event has the potential to negatively impact any rescue or fire suppression activities because it is likely to create significant physical obstacles and logistical challenges. With the probability of strong aftershocks, there exists a need to provide increased protection for anyone on upper floors. Geological conditions created by the numerous faults will result in increased fire danger to structures, delayed fire department response, and unique rescue challenges. Seismic events of sufficient magnitude will cause substantial damage to structures. These damages are likely to be accompanied by a substantial number of fires that may exceed the fire department suppression capabilities. Accordingly, built -in fire suppression systems provide the only adequate measure to mitigate the potential hazards from and damage caused by such fires. The County of Los Angeles is subject to occasional severe rainstorms. The impacts from these rainstorms are exacerbated if hillside areas have been burned by wildland fires because significant mud and debris flows can occur. Mud and debris flows can impair fire department access or delay response times if access roads are obstructed by mud or debris. TOPOGRAPHICAL - The topographical conditions of the County of Los Angeles includes many mountains, hills, and canyons which tend to accelerate the periodic high- velocity winds by means of a venturi effect. These canyon winds and the significant growth of vegetation of a combustible nature increase the fire danger. Additionally, long periods of dry, hot weather, combined with unpredictable seasonal winds (Santa Ana wind conditions) result in increased exposure to fire risk. The hillside areas have access roads that are narrow, steep, and contain many sharp curves, all of which makes timely response by large fire apparatus difficult. Ordinance No. 11 -946 Page 5 The specific sections of this code.that constitute' more restrictive building standards are identified in the table set forth below. The more restrictive building standards contained in this code and identified in the table below shall be applicable only in those cities served by the District which have ratified the aforesaid sections in accordance with California Health and Safety Code section 13869. Section Local Condition Explanation and Findings 304.1.2 - Climatic and Local amendment requiring brush clearance in order to Ve • etation Topographical maintain defensible space for fire operations that is necessary due to Los Angeles. County's unique climate and topography to reduce risk of fire and to minimize the spreading of fire to structures. 315.2.2.1 - Climatic Prevents storage of combustible materials under Storage under stairways to help prevent fire in stairways from stairways preventing safe exit in event of . fire. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions. 325.1.1 — Climatic and Local amendment requiring brush clearance under Support Topographical electrical transmission lines in order to prevent fires clearance caused by powerlines and to maintain defensible space for fire operations that is necessary due to Los Angeles County's unique climate and topography to reduce risk of fire and to minimize the spreading of fire to structures.. 325.1:2 — Line Climatic and ' Local amendment requiring clearance away from electrical clearance Topographical transmission lines in order to prevent fires caused by powerlines and to maintain defensible space for fire operations that is necessary due to Los Angeles County's unique climate and topography to reduce risk of fire and to minimize the s • readin • of fire to structures. 325.1.3 —, Self- Climatic and Local amendment requiring clearance of trees and other supporting Topographical growth from aerial cables in order to prevent fires and to aerial cable maintain defensible space for fire operations that is necessary due to Los Angeles County's unique climate and topography to reduce risk of fire and to minimize the spreading of fire to structures. 325.2.1 — Climatic and Local amendment creating defensible space for fire Clearances Topographical operations that is necessary due to Los Angeles County's unique climate and topography to reduce risk of fire and to minimize the s • readin • of fire to structures. 325.2.2 — Extra Climatic and Local amendment creating defensible space for fire Hazard operations that is necessary due to Los Angeles County's Topographical unique climate and topography to reduce risk of fire, to minimize impacts of fire in fire hazard severity zone, and to reduce possibility of wildland fires spreading to structures. 325.10 — Climatic and Local amendment requiring clearance of roadways to Roadway provide adequate access for firefighting apparatus, to Clearance Topographical create defensible space for fire operations, and to reduce the possibility of wildland fires spreadin • to structures Ordinance No. 11 -946 Page 6 Necessary due to Los Angeles County's unique climate and topography. 326.7 — Fire Climatic, Local amendment to require fire safety measures •rotection including but not limited to water supply, firebreaks facilities Geological, and posting of fire watchers, access roads, restriction of re • uired Topographical activities during high fire hazard and other conditions to maintain reasonable fire safety. Necessary due to Los Angeles County's unique climate and topography to reduce risk of fire, to reduce the possibility of wildland fires spreading to structures, and to minimize impacts of fire. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 326.12.2 - Climatic and Local amendment to reduce the threat of fires by requiring Chimneys Topographical spark arrestors on chimneys that is necessary due to Los Angeles County's unique climate and topography to reduce risk of fire and to minimize impacts of fire. Such spark arrestors reduce the likelihood of embers exiting a chimne and ignitinga fire. 326.14 — Climatic and Local amendment requiring clearance of roadways to Roadway provide adequate access for firefighting apparatus, to Clearance Topographical create defensible space for fire operations, and to reduce the possibility of wildland fires spreading to structures Necessary due to Los Angeles County's unique climate and topography. 503.1.2 — Climatic, Provides for additional access requirements necessary Additional Geological, and because of terrain, climate or other factors that limit access Topographical access. Necessary to ensure adequate response times due to the unique climatic and topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the prevalence of earth • uakes in Los Angeles Count . 503.2.1 — Climatic, Requires unobstructed clearance to so clearance on fire apparatus Dimensions Geological, and access roads with exception for protected tree species. Topographical Necessary to prevent obstruction of access roads by tree limbs or other obstructions and thus allow for quick response times to fires and other emergencies. Necessary to ensure adequate response times due to the unique climatic and topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 503.2.5 - Dead- Climatic, Provides for more stringent width, turning radius and ends Geological, and grade specifications for access roads to ensure access Topographical for fire apparatus. Necessary due to unique climatic and topographical conditions that increase the risk of fires. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 503.4 — Climatic, Adds speed bumps to list of prohibited obstructions to Obstruction of Geological, and fire apparatus access roads. Speed bumps reduce fire apparatus Topographical response times to fires and other emergencies because access roads fire apparatus have to slow down to pass over them or drive around them. Necessary to ensure adequate response times due to the unique climatic and 1 1 1 • Ordinance No. 11-946 Page 7 topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the prevalence of earth • uakes in Los An • eles Count . 503.4.1 - Climatic, Requires fire code official approval to install traffic Traffic Geological, and calming devices. Such devices can reduce response calming Topographical times to fires and other emergencies. Necessary to devices ensure adequate response times due to the unique • climatic and topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the • revalence of earth • uakes in Los An • eles Count 503.7 - Fire Climatic Requires additional fire protection systems including fire- protection in Geological, and flow and access, for recreational vehicle, mobile home, recreational Topographical and manufactured housing parks, sales lots, and • vehicle • storage lots. Necessary to ensure adequate water supply mobile home and access to such locations due to the unique climatic manufactured and topographical conditions that increase the risk of housing fires in fire hazard severity zones. Further necessary arks ales p, s because risk of fire is increased due to the prevalence of lo th and - an earthquakes in Los Angeles County. stora lots ge '504.5 - Roof Climatic. Provides various design and location requirements for to • access Geological, and solar photovoltaic systems installed on roofs of buildings and safety Topographical for residential and commercial structures. Access and spacing requirements ensure firefighter access to the roof, provide access pathways to specific areas of the roof, provide for venting cut-out areas, and to provide emergency egress from the roof. Necessary because of increased danger of fire in Los Angeles County due to climatic and topographical conditions. 7 ,, 507.5.1.1 - Pool Climatic, Requires a draft hydrant for swimming pools and spas draft system in Geological, and located in the fire hazard severity zone in order to provide • fire hazard Topographical a source of water to fight fires. Necessary because of severity zones. unique climatic and topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 507.5.10 -. Climatic, Provides posting of sign to notify fire department of draft • Draft System Geological, and hydrant for swimming pools and spas in fire hazard identification Topographical severity zone. Necessary because of unique climatic and sign topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 901.7.7 - Climatic, Prohibits obstruction of fire protection equipment. Obstruction to Geological, and Necessary because of unique climatic and topographical fire protection Topographical conditions that increase the risk of fires in fire hazard equipment severity zones. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 901.7.8 - Climatic, Provides signage requirements for water control valves in Above-ground Geological, and order to facilitate fire fighter identification and use of said water control To • o • ra • hical valves in an emer• enc . Necessa because of uni• ue Ordinance No. 11 -946 Page 8 valve signs climatic and topographical conditions that increase the risk of fires in fire hazard severity zones. Further necessary because risk of fire is increased due to the • revalence of earth • uakes in Los An • eles Count . 901.7.11 — Climatic, Provides clearance requirements for water control valves Clear space Geological, and in order to facilitate fire fighter identification and use of around above - Topographical said valves in an emergency. Necessary because of ground water unique climatic and topographical conditions that control valve increase the risk of fires in fire hazard severity zones. signs Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 903.1.2 — Climatic, Provides an additional level of protection to occupancies Occupancies in Geological, and Fire Hazard Topographical Severity Zones in case of a fire by requiring installation of automatic fire and in the sprinklers. Necessary because of unique climatic and Malibu- Santa topographical conditions that increase the risk of Monica catastrophic fires in fire hazard severity zones and due to Mountains or the topography that reduces response times to fires. San Gabriel Further necessary because risk of fire is increased due to South face the prevalence of earthquakes in Los Angeles County. areas 903.2.11.3 • Climatic and Provides an additional level of protection to occupancies Building over Geological in case of a fire by requiring installation of automatic fire three stories in sprinklers. Necessary because of large number of height buildings over three stories in Los Angeles County that increases the risk of fire due to damage or collapse of buildings due to the increased prevalence of earthquakes in Los Angeles County. 903.4.2 - Climatic and Requires installation of exterior fire alarm visual device. Alarms Geological Visual alarms are necessary to warn both disabled and non - disabled persons. Necessary because of increased likelihood of fires due to climatic conditions. Further necessary because risk of fire is increased due to the prevalence of earthquakes in the County. 903.7 — Climatic and Requires installation of devices for the automatic fire Geological Buildings Four sprinkler system within an exit stairway enclosure. or more Necessary because of increased likelihood of fires due to stories climatic conditions. Further necessary because risk of fire is increased due to the prevalence of earthquakes in the County_ 905.2.1 — Climatic Construction and installation requirements for Class I Class I standpipes; standpipes to ensure adequate fire protection systems 905.2.1.1, and water supply due to fires in Los Angeles County's hot 905.2.1.2; and windy climate. 905.2.1.3 905.4 - Climatic Installation /Regulation of Fire Protection System to Location of Class I ensure proper location of hose connection to control fires . standpipe hose in Los Angeles County's hot and windy climate. connections 905.5.3 - Class Climatic Installation and regulation of interior wet standpipes to 1 Ordinance No. 11 -946 Page 9 II System 1 1/2- ., ensure adequate fire protection system due to fires in Los inch. hose An • eles Count 's hot and wind climate. 905.6.1 - Climatic Local amendment regarding installation and regulation of Protection Fire Protection System to ensure proper location of hose connection to control fires in Los Angeles County's hot and windy climate. 905.6.1.1 - size Climatic Size requirements for Class III standpipes to ensure adequate fire protection system due to fires in Los An • eles Count 's hot and wind climate. 905.9 - Riser Climatic Additional requirements to fire protection system for shutoff valve.. testing, maintenance and operation to control fires in Los supervision Angeles County's hot and windy climate. and drain 905:12 - Climatic Requires installation and other guidelines related to inlets Basement pipe for fire protection systems in basements. Necessary. inlets, 905.12.1, because of increased danger of fire in Los Angeles County 905.12.2, due to hot and windy conditions. 905.12.4 .. 907.9.4.1 - Climatic. Prohibits concealing or obstructing fire alarm equipment. , Obstruction of Geological, and Necessary because of increased danger of fire in Los fire alarm Topographical Angeles County due to hot and windy conditions. Further equipment necessary because the risk of fire is increased due to the • revalence of earth • uakes in Los An • eles Count . 910.2 - Climatic Requires installation of smoke and heat vents in roofs of Where buildings or portions thereof occupied as Group F -1, S -1z req uired or containing high -piled combustible storage. Necessary because of increased danger of fire in los Angeles County due to hot and windy conditions. 910.2.1.1 — Climatic Requires smoke and heat removal for basement. level Grou • S -2 parking garages. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions. 910.4 — Climatic Requirements for mechanical smoke exhaust in buildings. Mechanical Necessary because of increased danger of fire in Los smoke Angeles County due to hot and windy conditions. exhaust 912.2.1 — Climatic. Requires fire department connections to be located within Visible Topographical 150 feet of a public fire hydrant and at a safe distance location Geological from the building. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions. Further necessary because the risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 912.7 — Climatic, Requires red paint on fire department connections subject ldentificatio Topographical to rust or corrosion in order to identify them to firefighters n — and protect from the elements. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions. 912.8 — Climatic, Requires breakable caps or plugs for fire hose couplings Breakable Topographical to protect them from the elements and to ensure easy ca • s or access to the fire department connection during fires. Necessary because of increased danger of fire in Los plugs An • eles Count due to hot and wind conditions. 914.9.1 - Climatic Requires Spray booths to have automatic fire sprinkler Spray booths system protection under specified conditions. Necessary Ordinance No. 11 -946 Page 10 because of increased danger of fire in Los Angeles County due to hot and windy conditions. Further necessary because the risk of fire is increased due to the . revalence of earth • uakes in Los An • eles Count . 1007.9.1 — Climatic, Requirements for signage warning against elevator use in Signage of high- Geological, and an emergency. Necessary to ensure proper notice and rise buildings Topographical evacuation in case of fire or other emergency. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions. Further necessary because risk of fire and need for evacuation is increased due to the prevalence of earthquakes in Los Angeles County. 1107.9 — Hell- Climatic; Provides for additional public safety evacuation /landing Topographical area on high -rise buildings. Necessary due to large number of high -rise buildings in Los Angeles County and stops for high difficulty in evacuating high -rise buildings in case of fire rise or other emergency. 1107.10 — Climatic; Provides for requirements for helistops in fire hazard Helistops in fire . Topographical severity zones to enable helicopters and associated water hazard severity tenders and support equipment to safely operate to zones; 1107.10.1 conduct operations to combat fires in those areas. Surface; Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions and topography that hinders the ability for fire apparatus to gain access to remote portions of the County. 1107.10.2 - Climatic; Provides for a hydrant next to helistops in fire hazard Hydrant Topographical severity zones to enable helicopters to fill their tanks to facilitate water drops on wildland fires in those areas. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions and topography that hinders the ability for fire apparatus to gain access to remote portions of the County. 1107.10.3 — Climatic. Provides for requirements for fire apparatus access to Access Topographical helistops in fire hazard severity zones to enable support equipment and apparatus associated with helicopter operations to combat fires in those areas. Necessary because of increased danger of fire in the County due to hot and windy conditions and topography that hinders the ability for fire apparatus to gain access to remote portions of the County. 1504.4 - Fire Climatic Provides for spray booths to be equipped with automatic Protection fire sprinklers. Necessary because of increased danger of fire in Los Angeles County due to hot and windy conditions. Sections 1603, Climatic and Provides requirements for fruit and crop ripening 1604, 1605, Geolo. ical operations to prevent ignition of ethylene gas and reduce 1606, 1607 — risk of fire and explosion. Necessary because of Fruit and Crop increased danger of fire in Los Angeles County due to hot Ripening and windy conditions and to reduce risk of fires and explosion from earthquakes. 1910 - Storage Climatic Provides requirements for the safe storage of combustible of Combustible pallets to reduce risk of fire. Necessary because of Idle Pallets , increased danger of fire in Los Angeles County due to hot 1910.10, 1910.2, and windy conditions. 1910.3, 1910.4, Ordinance No. 11 -946 Page 11 1910.5, 1910.6 Table 1910.4.1, Table 1910.4.2 Table 2306.2 Climatic and Provides for increased separation for aisles. Necessary Geological because of unique climatic conditions that increase the risk of fires. Further necessary because risk of fire is increased due to the prevalence of earthquakes in Los Angeles County. 2306.7.1 - Climatic Requires installation of smoke and heat vents. Necessary Vents because of increased danger of fire in Los Angeles Count due to hot and wind conditions. 2308.2.2 — Racks Climatic Provides for effectiveness of sprinkler systems by with solid prohibiting solid shelves, which would restrict water from shelving extinguishing fire on shelves. Necessary because of increased danger of fire in Los Angeles County due to climatic conditions. 2404.21 - Climatic and Increased clearance requirements for combustible Combustible vegetation near tents and membrane structures. Necessary vegetation: Topographic to increase fire and life safety around such structures and to create defensible space. Necessary because of fire risk due to climate and unique topography of Los Angeles County. 2605.9 — Geological Requirements for protective devices to be installed on fuel Backflash gas and oxygen lines to increase safety and reduce risk of Prevention explosion and fire. Necessary because risk of leaks or tank failure is increased due to the prevalence of earth • uakes in Los An • eles Count . .,, 2703.11.3.8 — Climatic and Creates requirements for floors in buildings where Floors hazardous materials are used or stored. Necessary to Geological increase fire and life safety and to minimize fire danger from hazardous materials. Necessary because risk of fire and spillage of hazardous materials is increased due to the • revalence of earth • uakes in Los An • eles Count . 3404.2.8.3 — Geolo•ical Requirements for secondary containment of flammable Secondary and combustible liquids that are necessary to increase Containment fire and life safety and to prevent fires involving flammable and combustible liquids from spreading. Necessary because risk of leaks or tank failure is increased due to the prevalence of earthquakes in Los Angeles County. 3404.2.8.16.1 — Climatic and Require foam deluge system. Necessary because of increased danger of fire in Los Angeles County due to System Geological climatic conditions and because risk of Teaks or tank requirements failure is increased due to the prevalence of earthquakes in Los Angeles County. 3404.2.9.1.1 - Geological and Requires all above - ground tanks exceeding 1,500 square Required foam Climatic feet of liquid surface area used for the storage of Class fire protection or Class II flammable liquids to be provided with foam fire systems protection. Necessary because of increased danger of fire in Los Angeles County due to climatic conditions and because risk of leaks or tank failure is increased due to the • revalence of earth • uakes in Los An • eles Count 3404.2.9.6.1.3 Geolo • ical and Provides for additional s • acin • between tanks to reduce Ordinance No. 11 -946 Page 12 - Location of Climatic fire danger and help prevent fire from spreading to tanks for adjacent tanks. Necessary because of increased danger boilover liquids of fire in Los Angeles County due to climatic conditions and because risk of leaks or tank failure is increased due to the • revalence of earth. uakes in Los An • eles Count . 3404.3.7.6 - Geological and Construction and fire access requirements for liquid Construction storage rooms. Necessary because of increased danger Climatic of fire in Los Angeles County due to climatic conditions and because risk of explosion or container failure is increased clue to the prevalence of earthquakes in Los An.eles Count . 3406.5.1.1 - Geological and Provides increased distances for bulk transfer and Location Climatic process transfer operations so that they are farther away from the public and other buildings. Necessary because of increased danger of fire in Los Angeles County due to climatic conditions and because risk of leaks or tank failure is increased due to the prevalence of earthquakes in Los An • eles Count 3406.5.1.19 - Geological and Class I, II, or III liquids shall be transferred from a tank Liquid Climatic vehicle or tank car only into an approved atmospheric transfer tank or approved portable tank. Necessary because of increased danger of fire in Los Angeles County due to climatic conditions and because risk of leaks or tank failure is increased due to the prevalence of earthquakes in Los Angeles County. 3804.4 - Geological and Requirements for LP gas storage tank distances. Multi • le Climatic Necessary because of increased danger of fire in Los container Angeles County due to climatic conditions and because installation risk of leaks or tank failure is increased due to the prevalence of earthquakes in Los -Angeles Count 4605.1 - tire Climatic and Creates requirements for fire access roads for outdoor storage yard; operations to enable fire apparatus to gain access to fight 4605.1.1 - Topographical fires. Necessary to increase fire and life safety and to access to piles; minimize risk of fire spreading beyond storage areas. 4605.1.2 Necessary because risk of fire due to climate and topography in Los Angeles County. 4907.1 - Climatic and Local amendment providing that defensible space General Topographical requirements shall also comply with Chapter 3 of this code. Necessary due to Los Angeles County's unique climate and topography to reduce risk of fire and to minimize impacts of fire in fire hazard severity zone. 4908.1 - Fuel Climatic and Local amendment creating defensible space for fire Modification Topographical operations that is necessary due to Plan in Fire Los Angeles County's unique climate and topography to Hazard reduce risk of fire and to minimize impacts of fire in fire Severity Zone; hazard severity zone. 4908.1.1 Plan Modification 5004 - fire Climatic and Creates requirements for fire access roads and storage apparatus requirements for tire storage in automobile wrecking yards. access roads; Topographical Necessary to enable fire apparatus and fire fighters to gain 5006 - access to fight fires and respond to emergencies. housekeeping; Necessary because risk of fire due to climate and 5008 tires' to•o•ra•h in Los An.eles Count . APPENDIX B Topographical and Provides for increased fire -flow to allow for more water to 1 1 1 1 1 Ordinance No. 11-946 Page 13 B105.1 — One- Climatic ., be available to fight fires. Necessary because of increased family danger of fire in Los Angeles County due to climatic and dwellings topographical conditions. • APPENDIX B Topographical and Provides for increased fire-flow to allow for more water to • B105.1.1 — Two- Climatic be available to fight fires. Necessary because of increased family • danger of fire in Los Angeles County due to climatic and dwellings topographical conditions.. APPENDIX B Topographical and Provides for increased fire-flow to allow for more water to B105.2 — Climatic be available to fight fires. Necessary because of increased Buildings other danger of fire in Los Angeles County due to climatic and than one-and topographical conditions. two-family dwellin . s APPENDIX .B Topographical and Provides for increased .fire-flow at mobile home parks in B105.3 — Mobile Climatic Very High Fire Hazard Severity Zones to allow for more home 'arks water to be available to fight fires. Necessary because of increased danger of fire in Los Angeles County due to climatic and to e o • ra . hical conditions. APPENDIX B Topographical and Provides for increased fire-flow for subdivisions of land to. B105.4 — Land Climatic allow for more water to be available to fight fires. . subdivision Necessary because of increased danger of fire in Los projects Angeles County due to climatic and topographical conditions. APPENDIX C. Topographical and Provides for hydrant spacing on streets to ensure hydrants Section C102.2 Climatic • are accessible to firefighters. Necessary because of — Location on increased danger of fire in Los Angeles County due to street climatic and topographical conditions. APPENDIX C, Topographical and Provides for hydrant spacing to ensure that water is Section C105.2 Climatic • available to fight fires. Necessary because of increased — One-family danger of fire in Los Angeles County due to climatic and dwelling topographical conditions. APPENDIX C, Topographical and Provides for hydrant spacing for cul-de-sacs to ensure that Section Climatic there is adequate water supply available to fight fires. C105.2.1 — Cul- Necessary because of increased danger of fire in the de-sac hydrant County due to climatic and topographical conditions. location • APPENDIX C, Topographical and Provides for hydrant spacing for buildings other than Section Climatic single family dwellings to ensure that there is adequate C105.2.2 — water supply available to fight fires. Necessary because of Buildings other increased danger of fire in the County due to climatic and than one-family topographical conditions. dwelling units. APPENDIX C, Topographical and Provides requirements for on-site hydrants to ensure that Section C106 — Climatic there is adequate water supply available to fight fires. On-site • Necessary because of increased danger of fire in Los hydrants Angeles County due to climatic and topographical conditions. • APPENDIX K — • Topographical and Provides various design and location requirements for Roof solar photovoltaic systems installed on roofs of buildings Obstructions Climatic for residential and commercial structures. Access and K103.1, K103.2, spacing requirements ensure firefighter access to the roof, K103.2.1 provide access pathways to specific areas of the roof, K103.2.1.1 K103.2.1.2, provide for venting cut-out areas, and to provide K103.2.1.3, emergency egress from the roof. Necessary because of K103.2.2, increased danger of fire in Los Angeles County due to Ordinance No. 11 -946 Page 14 K103.2.2.1, climatic and topographical conditions. K103.2.3, K103.2.4, K103.3, K103.4, K103.4.2, K103.2.1, K103.4.2.2, K103.4.2.3, K103.4.2.4, K103.4.3, K103.4.3.1, K103.4.3.2, K103.4.3.2.1, K103.4.3.2.2, K103.4.3.2.3, K103.4.3.2.4, K103.4.3.2.5, K103.4.3.2.6, K103.5, K103.5.1 Appendix Topographical and Provides various design and location requirements for roof K104.1, K104.2, Climatic gardens and landscaped roofs for residential and K104.2.1, commercial structures. Access and spacing requirements K104.2.2, ensure firefighter access to the roof, provide access K104.2.2.2, pathways to specific areas of the roof, provide for venting K104.2.2.3, cut -out areas, and to provide emergency egress from the K104.2.3, roof. Necessary because of increased danger of fire in Los K104.2.3.1, Angeles County due to climatic and topographical K104.2.3.2 conditions. K104.2.3.2.1, K104.2.3.2.2, K104.2.3.2.3, K104.2.3.2.4, K104.2.3.5, K104.2.3.6, K104.3 1 1