HomeMy Public PortalAbout382542C.I. FRAME & COVER 1/2" MIN. 1 TO 3 CEMENT TO SAND MORTAR MIX. (ALL BRICK STRUCTURES) A P"p''. o D 0_' ° D' 0. 0 0. 4 D 8" 0. o D o ;D o o D CLASS "A" CONCRETE NOTES: 1) INSIDE OF BRICK MANHOLES TO BE PLASTERED WITH 1/2" MIN. 1 TO 3 CEMENT TO SAND MORTAR MIX TO TOP OF LARGEST PIPE. 2) MANHOLE STEPS UNIFORMLY SPACED AT MAX. 16"C-C. 3) GRANULAR BEDDING REQUIRED AROUND PIPE AT MANHOLES. 0..v o0 4 0. 4 PLAN 4) THE MINIMUM INSIDE DIAMETER FOR THE BASE AND RISER SECTIONS SHALL BE 42" FOR 8" DIAMETER SANITARY SEWERS AND ALL STORM SEWERS. THE MINIMUM INSIDE DIAMETER FOR INSIDE DROP MANHOLES AND SANITARY SEWERS LARGER THAN 8" DIAMETER IS 48 INCHES. 31/4" MORTAR BED 1 f TOP TRANSITION A D = DIA. OF LARGEST PIPE APPROVED PATENTED WATER STOP REQUIRED FOR PLASTIC PIPE. SECTION A —A 1/2" MIN. 1 TO 3 CEMENT TO SAND MORTAR MIX. (ALL BRICK STRUCTURES) PLACE STEPS ON UNOBSTRUCTED WALL. LINE MANHOLE PIPE SEWERS 8"-24" DIA. METROPOLITAN ST. LOUIS SEWER DISTRICT Standard Details of Sewer Construction Dr. WSH/SAM Ch. J.C.K. 2009 SHEET 10